A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual
Page 34
A Series
®
Lighting Controller Modbus Register Map
Lighting Group Objects
28
22
4023
Astro On Enable
Int
On/Off
RW
23
4024
Astro Off Enable
Int
On/Off
RW
24
4025
BYTE
Astro On Offset
Int
0 – 254
RW
25
4026
LONG
Astro On Calc Hi** Word
0 – 254
R
26
4027
Astro On Calc Lo** Word
0 – 254
R
27
4028
BYTE
Astro Off Offset
Int
0 – 254
RW
28
4029
LONG
Astro Off Calc Hi** Word
0 – 254
R
29
4030
Astro Off Calc Lo** Word
0 – 254
R
30
4031
BYTE
FlickWarnEnable
Word
1-On / 0-Off
RW
31
4032
BYTE
FlickWarnTime
Word
0 – 240 min
RW
32
4033
WORD
FlickWarnPAEnble
Word
0 – 65535
RW
33
4034
WORD
FlickWarnInputEnb Word
0 – 65535
RW
Array of 33
Output Ref/
Switch Ref
pairs
Lighting Outputs
Output Ref
34
4035
Panel Number
Word
1 – 99
RW
35
4036
Object Type
4 – [BO]
303 – [LG]
RW
36
4037
Object Instance
Word
1 – 65535
RW
Switch Ref
37
4038
Panel Number
Word 1 – 99
RW
38
4039
Object Type
3 – [BI]
13 – [MI]
RW
39
4040
Object Instance
Word 0 – 65535
RW
40
4041
Value
Word
RW
41
4042
Switch Value
Word
RW
42
4043 – 4298
32 more entries:
8 registers per entry
RW
298
4299
Common Off Time Int
0 – 1000
RW
Array of 16
Common Groups
299
4300
Panel Number
Word 1 – 99
RW
300
4301
Object Type
Word 303 – [LG]
RW
301
4302
Object Instance
Word 1 – 16
RW
302
4303
Value
Word
RW
303
4304 – 4363
15 remote LG refs:
4 registers per entry
RW
363 registers / LG
Table 48. Lighting Group setup registers.