H-80 Function at Stop

Option:

Function:

Select the frequency converter function after a stop command or after the speed is ramped down to the
settings in par. H-81 Min Speed for Function at Stop [RPM].

[0] *

Coast

Leaves motor in free mode.

[1]

DC Hold/Motor Preheat

Energizes motor with a DC holding current (see par. B-00 DC Hold Current).

P-04 Auto Tune

Option:

Function:

The Auto Tune function optimizes dynamic motor performance by automatically optimizing the advanced
motor parameters par. P-30 Stator Resistance (Rs) to par. P-35 Main Reactance (Xh)) while the motor is
stationary.

[0] *

Off

No function

[1]

Full Auto Tune

performs Auto Tune of the stator resistance R

S

, the rotor resistance R

r

, the stator leakage reactance X

1

,

the rotor leakage reactance X

2

and the main reactance X

h

.

[2]

Reduced Auto Tune

performs a reduced Auto Tune of the stator resistance R

s

in the system only. Select this option if an LC

filter is used between the frequency converter and the motor.

Activate the Auto Tune function by pressing [Hand ] after selecting [1] or [2]. After a normal sequence, the display will read: “Press [OK] to finish Auto Tune”. After
pressing the [OK] key the frequency converter is ready for operation.

Note:

For the best results of the frequency converter, run Auto Tune on a cold motor

Auto Tune cannot be performed while the motor is running

NB!
It is important to set motor par. P-## Motor Data correctly, since these form part of the Auto Tune algorithm. An Auto Tune must be performed to achieve
optimum dynamic motor performance. It may take up to 10 min., depending on motor power rating.

NB!
Avoid generating external torque during Auto Tune

NB!
If one of the settings in par. P-## Motor Data is changed, par. P-30 Stator Resistance (Rs) to par. P-39 Motor Poles, the advanced motor parameters, will return
to default setting.
This parameter cannot be adjusted while the motor is running

NB!
Full Auto Tune should be run without filter only while reduced Auto Tune should be run with filter.

AF-600 FP High Power Operating Instructions