33

500B

SRC x Product Type

0 to 2

---

1

F716

0 (Low Voltage

Switchgear)

500C

SRC x NodeProt Rating Switch

0 to 65535

---

1

F001

0

500D

SRC x NodeProt LT Setting

0 to 655.35

---

0.01

F001

0

500E

SRC x NodeProt IOC Threshold Setting

0 to 655.35

---

0.01

F001

0

500F

SRC x NodeProt Ground Fault Setting

0 to 1

---

1

F102

0 (Disabled)

5010

SRC x NodeProt Short Time Setting

0 to 1

---

1

F102

0 (Disabled)

5011

SRC x Node Internal Diagnostics

0 to 65535

---

1

F701

0

5012

SRC x Node System Diagnostics 1

0 to 65535

---

1

F702

0

5013

SRC x Node System Diagnostics 2

0 to 65535

---

1

F703

0

5014

SRC x Node Hardware Diagnostics

0 to 65535

---

1

F704

0

5015

SRC x Node Physical Status

0 to 65535

---

1

F708

0

5016

SRC x Node Logic and Trip Status

0 to 65535

---

1

F709

0

5017

SRC x Node Last Trip Sequence Number

0 to 4294967295

---

1

F003

0

5019

SRC x Reflected CPU Diagnostics

0 to 65535

---

1

F706

0

501A

SRC x Reflected CPU 0 Command

0 to 65535

---

1

F707

0

501B

SRC x Reflected CPU 1 Command

0 to 65535

---

1

F707

0

501C

SRC x Fan Status

0 to 1

---

1

F108

0 (Off)

501D

SRC x CT Rating Node Report

0 to 65535

---

1

F001

0

501E

SRC x Node Serial Number

---

---

---

F205

(none)

5024

SRC x Node Status Reserved (43 items)

0 to 1

---

1

F001

0

504F

...Repeated for module number 2

509E

...Repeated for module number 3

50ED

...Repeated for module number 4

513C

...Repeated for module number 5

518B

...Repeated for module number 6

51DA

...Repeated for module number 7

5229

...Repeated for module number 8

5278

...Repeated for module number 9

52C7

...Repeated for module number 10

5316

...Repeated for module number 11

5365

...Repeated for module number 12

53B4

...Repeated for module number 13

5403

...Repeated for module number 14

5452

...Repeated for module number 15

54A1

...Repeated for module number 16

54F0

...Repeated for module number 17

553F

...Repeated for module number 18

558E

...Repeated for module number 19

55DD

...Repeated for module number 20

562C

...Repeated for module number 21

567B

...Repeated for module number 22

56CA

...Repeated for module number 23

5719

...Repeated for module number 24

Advertising