Power break, Circuit breakers chapter 2. breaker operation – GE Industrial Solutions Power Break I 800-2000 Frames 240-600 VAC User Manual

Page 13

Advertising
background image

Power Break

®

Circuit Breakers

Chapter 2. Breaker Operation

7

All breakers provided with tap cards are shipped with both

HIGH

(100% of the current rating

Sensor Amp

on the

breaker name plate) and

low

(50–75% of the current

rating

Sensor Amp

on the breaker name plate). The

low

card is packed and supported on the breaker handle. The

high

card is installed in the breaker frame. To change

settings use the following procedure:

W

W

W

WA

A

A

AR

R

R

RN

N

N

NIIIIN

N

N

NG

G

G

G:::: The circuit breaker must be removed from

the electrical system before attempting any operations
that involve removing the breaker’s cover.

1

1

1

1.... Turn the breaker

off

.

2

2

2

2.... Remove the four cover mounting screws and remove

the top cover. On motor operator-equipped breakers,
remove only the top cover.

3

3

3

3.... Withdraw the card from the tap changer support and

replace with the other card, as shown in Figure 10.
The print on the top of the card should be oriented
the same as the breaker cover name plate.

Figure 10. Cover and trip unit removed from the breaker.

4

4

4

4.... Trip units providing ground fault protection must

also have the tap setting changed on the tapped neu-
tral CT (four-wire systems). Change the black wire
lead from the

high

or

low

terminal to match the

desired tap setting of the breaker frame, as shown in
Figure 11.

5

5

5

5.... Replace the breaker cover.

6

6

6

6.... Operate the breaker manually through the

charge–close–open

cycle to ensure that the breaker is

properly functioning mechanically before energizing
or connecting it to the electrical system.

N

N

N

NO

O

O

OT

T

T

TE

E

E

E:::: A deenergized undervoltage release will not allow

the mechanism to charge and close.

7

7

7

7.... Store the extra tap card in a convenient place.

Figure 11. Neutral CT connection for four-wire ground fault.

Neutral Current Transformer (Four-Wire Ground
Fault System)

Ground fault protection is offered as an optional function
of the MicroVersaTrip® trip unit. However, all MicroVer-
saTrip-generation breaker frames are provided with ter-
minal board points for connection to a neutral CT.

D o

not short these terminals if there is no neutral CT
connected.

Always match the rating of the CT to the rating of the cir-
cuit breaker; specifically, use the following criteria:

Fixed-rated breaker frames – match the neutral CT
amp rating to the breaker sensor amp rating.

Tapped or high/low-rated breaker frames – match
the neutral CT amp rating to the

high/low

setting of

the breaker sensor amp rating.

Note that MicroVersaTrip RMS-9-equipped breakers are
not available with inverted construction (formerly desig-
nated by Cat. No. suffix B). These breakers may be either
top fed, as illustrated in Figure 12, or bottom fed, as illus-
trated in Figure 13.

N

N

N

NO

O

O

OT

T

T

TE

E

E

E:::: The neutral CT is mounted in reverse in Figure

13 when the breaker is bottom (reverse) fed.

C

C

C

CA

A

A

AU

U

U

UT

T

T

TIIIIO

O

O

ON

N

N

N:::: Match the tapped terminal for the black lead

to the tap setting, if provided, on the breaker frame.

C

C

C

CA

A

A

AU

U

U

UT

T

T

TIIIIO

O

O

ON

N

N

N:::: Observe the polarity markings on the neutral

CT shell and the breaker frame.

C

C

C

CA

A

A

AU

U

U

UT

T

T

TIIIIO

O

O

ON

N

N

N:::: When a neutral CT is not used or not

required (three-wire ground fault),

do not short the

ground fault terminal points on the breaker frame.
Leave them open as supplied by the factory.

Advertising