High power service manual for unit sizes 6x, 7 tips and tricks – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual

Page 19

Advertising
background image

The following control signals will still be available when [Hand] is activated:

[Hand] - [Off] - [Auto] - [Reset] keys

Coasting stop inverse (motor coasting to stop)

Reversing

Set-up select

Stop command from serial communication

Quick stop

DC brake

Off Stops the connected motor. The key can be Enabled [1] or Disabled [0] in par. K-41 [Off] Button on Keypad. If no external stop function is selected and the OFF
key is inactive the motor can only be stopped by disconnecting the mains supply.
[Auto] Enables the controller to be controlled via the control terminals and/or serial communication. A start signal applied on control terminals and/or the serial
bus will start the controller. The key can be Enabled [1] or Disabled [0] in par. K-42 [Auto] Button on Keypad.

NB!
An active HAND-OFF-AUTO signal via digital inputs has higher priority than the [Hand] and [Auto] control keys.

Reset This resets the controller after an alarm condition has been cleared. For an alarm (trip), power must be recycled to the controller before pressing the reset
key. The key can be Enabled [1] or Disabled [0] in par. K-43 [Reset] Button on Keypad.

2.2.7 Tips and Tricks

*

For the majority of applications the Quick Menu, Quick Set-up and Function Set-up provides the simplest and quickest access to all the
typical parameters required.

*

Whenever possible, performing an Auto tune will ensure best shaft performance.

*

Display contrast can be adjusted by pressing [Status] and [

] for a darker display or by pressing [Status] and [

] for a brighter display.

*

Under [Quick Menu] and [Changes Made], any parameter that has been changed from factory settings is displayed.

*

Press and hold the [Main Menu] key for 3 seconds to access any parameter

*

For service purposes, it is recommended to copy all of the parameters to the Keypad, see par. K-50 Keypad Copy for further information.

Table 2.1: Tips and tricks

NB!
Exchanging or adding a new control card, power card, or option card -- or updating the card's software - requires a manual restore of the drive for proper
operation.

High Power Service Manual for Unit Sizes 6x

18

2