GE Industrial Solutions Spectra Series Power Panelboards AMCB4GB and AMCB6GB User Manual

Page 2

Advertising
background image

2. Locate the side of the interior with a 2.75-inch

reference distance.

The circuit breaker straps are

mounted on the side of the panel interior bus at
which the distance from the vertical bus face to the
inner face of the bus-support rail is 2.75 inches, as
indicated in Figure 2.

Figure 2. Illustration of the 2.75-inch reference distance.

3. Assemble antiturn clips onto carriage bolts.

Slide an

antiturn clip [4] over the square shank of each
carriage bolt [14], as shown in Figure 3. Figure 4
illustrates the installation of a bolt and antiturn clip
onto the interior, as called for in the remaining steps.

Figure 3. Assembling an antiturn clip [4] with a carriage bolt [14].

Figure 4. Installing a carriage bolt [14] and antiturn clip [4] into the

interior.

NOTE:

For three-phase installations, continue

with step 4. For two-pole installations, proceed
to step 5.

4. Three-phase installations.

Use the following procedure

for all three-phase installations (kit AMCB6GB).

4a. Install carriage bolt assemblies.

Position the

carriage bolt [14] and antiturn clip [4] assemblies
as shown in Figures 5 and 6.

Figure 5. Carriage bolt and antiturn clip installation for three-phase

connections.

Figure 6. Carriage bolt and antiturn clip installation for three-phase

connections, isometric view.

4b. Install straps.

Place the G frame straps [5, 6] over

the carriage bolts and antiturn clips, as shown in
Figures 7 and 8. Place conical washers [7] on the
bolts and secure with nuts [11]. Leave the
connections finger tight.
If the group assembly selection is three-phase and
the assembly looks like Figure 8, then go to step 6.

Figure 7. Installing the straps for three-phase connections.

Figure 8. Installing the straps for three-phase connections, isometric

view.

Edge of G

Frame

Edge of G

Frame

Edge of G

Frame

Edge of G

Frame