Appendix: additional information – GE Industrial Solutions Power Break Stationary Conversion Kit User Manual

Page 4

Advertising
background image

4

Appendix: Additional Information

Table 1: Weights of Various PBII Breaker Frame Sizes

Frame

Rating

Operation

Type

Weight (lbs)

800A

Manual

Electrical

71
80

1600A
2000A

Manual

Electrical

79
88

2500A

Front Connect

Manual

Electrical

178
187

2500A

Back Connect

Manual

Electrical

167
176

3000A

Back Connect

Manual

Electrical

179
188

3000A

Front Connect

Manual

Electrical

216
225

4000A

Manual

Electrical

320
329

Table 2: Bolt Sizes and Recommended Mounting Torques for Bus Connections.

Frame Rating

Bolt

Torque (in-lbs)

800A

(1) ½ in

300

1600A-2000A

(2) ½ in

300

2500A

(4) 3/8 in

225

3000A

(4) 3/8 in

225

4000A

(6) ½ in

300

Table 3: Minimum Ventilation Cutout Areas

PBI

PBII

Stationary Total

Top

Bottom

Total

Top

Bottom

800A

N/A

N/A

N/A

N/A

N/A

N/A

1600A

60

30

30

60

30

30

2000A

160

80

80

86.4

43.2

43.2

2500A

160

80

80

160

80

80

3000A

270

135

135

270

135

135

4000A

280

140

140

270

135

135


GE Industrial Solutions

General Electric Company

41 Woodford Ave., Plainville, CT 06062

DEH41502 R01 © 2010 General Electric Company

These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in
connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not
covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.

Advertising