Pim400 series; atca board power input modules, Data sheet, Digital interface specifications – GE Industrial Solutions PIM400 Series User Manual
Page 6: General specifications
![background image](/manuals/295638/6/background.png)
GE
Data Sheet
PIM400 Series; ATCA Board Power Input Modules
-36 to -75 Vdc; 400W/10A
June 20, 2013
©2013 General Electric Company. All rights reserved.
Page 6
Digital Interface Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Feature Descriptions for additional information.
Parameter
Conditions
Symbol
Min
Typ
Max
Unit
Digital Signal Interface Characteristics
Clock frequency range
f
CLK
100
400
kHz
Measurement Tolerance
Feed Voltage A/B (-48V_AF & -48V_BF)
+/-3
%
Holdup Voltage (V_HLDP)
+/-3
%
-48V_OUT current (-48V_IOUT)
% of Io,max
+/-3
%
Module Temperature (TEMP)
+/-3
0
C
General Specifications
Parameter
Device
Min
Typ
Max
Unit
Calculated MTBF (P
O
=0.8P
O, RATED
, 48V
IN
, T
A
=40°C, Airflow=300LFM)
Telecordia Issue 2 Method 1 Case 3
All
2,308,563
Hours
Weight
28.3 (1.0)
g (oz.)