Pim400 series; atca board power input modules, Data sheet, Digital interface specifications – GE Industrial Solutions PIM400 Series User Manual

Page 6: General specifications

Advertising
background image

GE

Data Sheet

PIM400 Series; ATCA Board Power Input Modules

-36 to -75 Vdc; 400W/10A

June 20, 2013

©2013 General Electric Company. All rights reserved.

Page 6

Digital Interface Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions. See
Feature Descriptions for additional information.

Parameter

Conditions

Symbol

Min

Typ

Max

Unit

Digital Signal Interface Characteristics
Clock frequency range

f

CLK

100

400

kHz

Measurement Tolerance

Feed Voltage A/B (-48V_AF & -48V_BF)

+/-3

%

Holdup Voltage (V_HLDP)

+/-3

%

-48V_OUT current (-48V_IOUT)

% of Io,max

+/-3

%

Module Temperature (TEMP)

+/-3

0

C

General Specifications

Parameter

Device

Min

Typ

Max

Unit

Calculated MTBF (P

O

=0.8P

O, RATED

, 48V

IN

, T

A

=40°C, Airflow=300LFM)

Telecordia Issue 2 Method 1 Case 3

All

2,308,563

Hours

Weight

28.3 (1.0)

g (oz.)