When replacing batteries, replace with 12Volt/34Watt cell and exact quantity as listed below based on UPS VA rating:

600VA – 2 batteries

1000VA – 2 batteries

1500VA – 3 batteries

2000VA – 4 batteries

Please call your local GE representative for pricing and availability.

9.5 Hot Swappable Battery Replacement

Tower Procedure -

Step

1.

Remove front cover panel; pull out from top where finger grooves are located on each side. (See diagrams below)

600 & 1000VA

1500 & 2000VA

Step 2.

Push down slightly to allow front cover to be moved to the side. (See diagrams below)