13-7
Data subject to change without notice 7/07. © 2007 GE Drives
Name
Relay output card
Type
OPCG11SRY
Function
Converts transistor output signals from drive control output terminals Y1 to Y4 to relay (1SPDT) output signals
Specifications Input
None
Output
Four-channel contact (12 terminals from Y1A to Y4C) 250 Vac, 0.3 A, cos dia. = 0.3 A
Power Source
The power source to drive the relay card is supplied from the drive
Connection
Diagram
Remarks
Relay output contacts used in ac voltage control circuit logic
Includes four relay output circuits
RY
+ 13Vdc
5G
Y1A
Y1C
Y1B
5G
5G
5G
Connector
+ 24Vdc
CM
RY
+13Vdc
Y2A
Y2C
Y2B
+24Vdc
CM
RY
+13Vdc
Y3A
Y3C
Y3B
+24Vdc
CM
RY
+13Vdc
Y4A
Y4C
Y4B
+24Vdc
CM
Advertising