3.3 Technical data tables

Table 1. Technical data, type Gerapid 8007R & Gerapid 10007R

Parameter

Reference

Gerapid 8007 R

Gerapid 10007 R

Arc

chute

type

N/A

1x2 1x3 1x2 1x3

Rated continuous current [A]

ANSI C37.14 p.5.3

6.000

6.000 8.000 8.000

2

hours

current

[A]

N/A

7.200 7.200 9.600 9.600

2 minutes current [A]

N/A

12.000

12.000

16.000

16.000

20 seconds current [A]

N/A

18.000

18.000

24.000

24.000

Rated short-time current (250ms) [kA]

ANSI C37.14 p.5.5

90 (149 peak)

60 (100 peak)

90 (149 peak)

60 (100 peak)

Rated maximum voltage [V]

ANSI C37.14 p.5.2

800

1200

800

1.200

Rated insulation voltage - U

Nm

[V]

EN 50124-1 p.1.3.2.4

2.000 2.000 2.000 2.000

Rated impulse voltage - U

Ni

[kV]

EN 50124-1 p.1.3.2.7

18 [1,2/50 µs]

18 [1,2/50 µs]

18 [1,2/50 µs]

18 [1,2/50 µs]

Power frequency voltage – U

a

[kV]

EN 50124-1 a.B 2.2

10 [1 minute 50 Hz] 10 [1 minute 50 Hz] 10 [1 minute 50 Hz] 10 [1 minute 50 Hz]

Mechanical endurance [cycles]

a)

N/A

10.000 10.000 10.000 10.000

Rated short circuit peak / sustained current [kA]

c)

ANSI C37.14 p.5.4

200 / 120

132 / 80

200 / 120

132 / 80

Short-circuit characteristic

Tests a, b, c, d ANSI C37.14 annex A

High-speed High-speed High-speed High-speed

Maximum arc voltage [V]

N/A

2.500

2.500

2.500

2.500

Mass ca.

N/A

220 kG

220 kG

220 kG

220 kG


a)

10.000 cycles without parts replacement. Inspection after 5.000 cycles. Max. 5.000 cycles by means of ED impulse coil or POCT release.

c)

Trip by means of POCT (direct-acting, instantaneous, electromechanical and polarized OC release) or by means of ED impulse coil with no intentional delay.

2010-02-16 DTR01807 rev.02