Infinity D Power System Installation Guide: +24V Systems

H2007001

Issue 2.0, June 4, 2009

71

Manual Contactor Control and Alarms

WARNING: If this is an operating plant with loads, skip this test.

Step

Action

1.

Open the contactor by controller command (MENU > CONTROL / OPERATIONS >
DISCONNECTS).

2.

Verify the controller reports a Contactor Open alarm.

3.

Close the contactor by controller command.

4.

Verify the alarms clear and the controller returns to Normal.

Automatic Contactor Control and Alarms

WARNING: If this is an operating plant with loads, skip this test.

Step

Action

1.

Check the disconnect thresholds (MENU > CONTROL / OPERATIONS >
DISCONNECTS).

2.

Adjust the float voltage to a value less than this threshold (MENU > CONFIGURATION >
FLOAT SETTINGS > SET POINT).

3.

Disconnect the batteries in the plant.

4.

Verify the battery disconnect opens and the controller reports a Contactor Open alarm.

5.

Restore the plant voltage back to its original setting.

6.

Verify the contactor closes.

5.

Verify the alarms clear and the controller returns to Normal.