1–8 supported ieds – GE Industrial Solutions POWER LEADER PMCS Network Architecture Guide User Manual

Page 17

Advertising
background image

Power Management Control System

Chapter 1 – Introduction

7

1–8 Supported IEDs

PMCS supports a wide variety of GE and third-party
power management IEDs. These IEDs are listed in
Table 1, along with their function, communications

protocol, and maximum communications speed for
Modbus-based IEDs (Commnet IEDs must
communicate through the Modbus Concentrator).

IED Name

IED Name

IED Name

IED Name

Function

Communications Protocol (Modbus Speed)

239 Motor Protection Relay

Protection/Control

Modbus RTU (19.2 Kbaud)

269 Plus Motor Management Relay

Protection/Control

Modbus RTU (2400 baud)

565 Feeder Management Relay

Protection/Control

Modbus RTU (9600 baud)

735 Feeder Relay

Protection/Control

Modbus RTU (19.2 Kbaud)

GE-Zenith Generator PLC (Series 90-70)

Metering/Control

Modbus RTU (19.2 Kbaud)

GE-Zenith MX200 (Microprocessor Controller)

Protection/Control

Modbus RTU (19.2 Kbaud)

EPM 7330

Metering

Modbus RTU (19.2 Kbaud)

EPM 3710 Meter

Metering

Modbus RTU (19.2 Kbaud)

EPM 3720 Meter

Metering

Modbus RTU (19.2 Kbaud)

EPM 7300 Meter

Metering

Modbus RTU (19.2 Kbaud)

EPM 7700 Meter

Metering/Control

Modbus RTU (19.2 Kbaud)
Note: Native Ethernet device.

EPM 5000P Meter

Metering

Modbus RTU (9600 baud)

EPM 5200P Meter

Metering

Modbus RTU (9600 baud)

EPM 5300P Meter

Metering

Modbus RTU (9600 baud)

EPM 5350P Meter

Metering

Modbus TCP (Ethernet 10BaseT, RJ-45)

EPM 9450Q Meter

Metering/Control

Modbus RTU (38.4 Kbaud)

Modbus TCP (Ethernet 10BaseT, RJ-45)

EPM 9650Q Meter

Metering/Control

Modbus RTU (38.4 Kbaud)

Modbus TCP (Ethernet 10BaseT, RJ-45)

GE Fanuc PLC 90/30

Protection/Control

Modbus RTU (19.2 Kbaud)

GE Fanuc PLC 90/70

Protection/Control

Modbus RTU (19.2 Kbaud)

GE Fanuc PLC Micro 90

Protection/Control

Modbus RTU (19.2 Kbaud)

Universal Relay

Protection/Control

Modbus RTU (19.2 Kbaud)

MicroVersaTrip-C and -D Trip Units

Metering/Protection

commnet (requires Modbus Concentrator)

Modbus Concentrator

Communications

Modbus RTU (19.2 Kbaud)

POWER LEADER Electronic Power Meter

Metering

Modbus (19.2 Kbaud) or commnet
(commnet requires Modbus Concentrator)

POWER LEADER Junction Box

Communications

commnet (requires Modbus Concentrator)

POWER LEADER Repeater

Communication

commnet (requires Modbus Concentrator)

Power Quality Meter (PQM)

Metering

Modbus RTU (19.2 Kbaud on 1 or 2 ports)

Advertising