3.9.5

RPA system - Control bus connection

WARNING !

This operation must be performed by trained personnel before the initial start-up
(ensure that the UPS installation is completely powered down).


Access to the RPA board

1 - Open the front door A of the cabinet.

2 - Remove the protection covers B, C, D” fixed

with screws F.

F

F

F

B

C

D

Fig. 3.9.5-1 Access to the RPA board

NOTE !

When fixing again the protection
covers, make sure that the screws
“F”
are as tight as possible since
they serve also as earth
connection.


LP33S_010-020_S5_RPA connection_GE_02GB

P16

J4

J3

UPS 1

UPS 2

P16

J3

J4

UPS 3

P16

J3

J4

P16

UPS 4

J4

J3

P2

P2

P2

P2

P15

P15

P15

P15

Fig. 3.9.5-2 Bus connection RPA parallel system

Bus connection RPA parallel system
Connect the control bus cable between the parallel units as indicated in the diagram Fig. 3.9.5-2.

Provide that the connectors J3 and J4 are properly fixed with the included screws.

NOTE !

The jumper JP1 - JP2 - JP3 must be
removed only on the intermediate
units, where the connectors J3
and J4
are both inserted.
Do not insert or remove J3
and J4
from the board “P16 - Connector
adapter RPA”
when the parallel
system is operating.

LP33S_010-020_S5_RPA connection_03

J3

J4

JP2

JP1

JP3

P16

Fig. 3.9.5-3 Connection to Board P16