EPM 4500 SUB METER – INSTRUCTION MANUAL

MODBUS COMMUNICATIONS

CHAPTER 4: COMMUNICATIONS

• Power: kW, kvar, and kVA
• Power Factor

4.1.7

32-bit Long and Float Data Formats

The EPM4500 supports standard format for 32-bit Long (signed or unsigned). The first of
the two 16-bit Modbus register set contains the HIGH order 16 bits of the 32-bit Long data.
The second of the two 16-bit Modbus register set contains the LOW order 16 bits of the 32-
bit Long data.

The EPM4500 supports Intel 32 bit (IEEE) FLOAT format. That means, unlike the standard
Long format, the first of the two 16-bit Modbus register set contains the LOW order 16 bits
of the 32-bit Float data. The second of the two 16-bit Modbus register set contains the
HIGH order 16 bits of the 32-bit Float data.