Continued), Table 1: af-300c standard specifications – GE Industrial Solutions AF-300C AC Drive User Manual

Page 22

Advertising
background image

lnverters

GEK-85716

TABLE 1: AF-300C

STANDARD SPECIFICATIONS

(continued)

ITEM

SPECIFICATION

inverter HP

CONTROL: (continued),

Torque Limit Control

40 50 60 75

100 125 150 175 200 250 300

Output current can be limited within a range of approximately 30% to 150%

(1% step).

Automatic Acceleration and

Operation

Slip Compensation Control

Multi-Step Frequency Setting

Can be used to avoid DC Link overvoltage trips caused by motor

regeneration during deceleration.

Maintains motor at constant speed with load fluctuations.

Seven adjustable frequency presets can be selected via three external

contacts.

Up-Down Control

External momentary contacts can be used to control frequency increase
decrease.

Momentary Power Failure Restart

inverter Bypass Logic

Bias Frequency Setting

Frequency Jump

Reversing Operation By Frequency
Setting Signal Characteristics

Upper and Lower Limiters of

Output frequency can be limited to a specified range (overiding frequency

Output Frequency

reference).

PFiOTECTiON/DETECTiON:

OPERATION:

Frequency Reference Signals

input Signals

Output Signals

After momentary power failure, automatic restart is possible.

Allows switching the motor between the inverter and the power line.

Magnitude of the bias added to the frequency reference signal can be set

from 0 to 100% (1% step).

Up to three resonant frequencies can be skipped. Width adjustable from
0 5 Hertz

step).

Makes bipolar frequency reference input possible. (Reverse motor rotation
by changing frequency reference voltage polarity, rather than by using
REV-CM contact.)

Stall Prevention, Overcurrent, Overvoltage, Undervoltage,
instantaneous Power Failure, lnverter Overload, Motor Overload (electronic

thermal action), External Failure (external thermal action), CPU Abnormal,

Output Short Circuit, Ground Fault (for inverter protection only), and Input
Surge.

Frequency Reference (Voltage Input): 0 to

VDC (0 to

Current input: 4 to 20 Ma DC.

Forward Command, Reverse Command, Self-Holding Selection, Current
Input Selection, Multi-Frequency Setting, Up-Down Control,

Selection, Free-Run Command, lnverter Bypass Command, Output Switch
Interlock Selection, External Alarm input, Alarm Reset Input, and Ground
Protection Input.

Contact Outputs:

Open Collector
outputs:

Power-Side (or Motor-Side) electromagnetic

command, Fault Relay Output..

See Section 6, Function Code 45.

Bias does not affect operation when frequency command comes from the Keypad Panel.

2-6