TECHNOFORCE Installation, Operation, and Maintenance

15

Installation

4.10 Set up & features

Note: Many sections of the Set up & Features show a path for navigation. An example is shown below to

understand the given path.
Example for system setup path.
Path: Status Screen / Setup(3) / System(3)
To follow the above path press the SETUP/3 key from the system status screen. Then press the SETUP/3 key

for number 3 which is a selection number for system and press ENTER key. It will lead to the system setup

screen.
Upon powering up the controller, the display will light and show the following screen:

<TECHNOFORCE PUMP>

CONTROLLER

MM/DD/YY HH:MM:SS A/P

STOP MANUAL NORM

The current date and time will be displayed on the third line.
Press the

SETUP/3 key once and the following MAIN SET UP menu items will be displayed:

SELECTION: # 0=EXIT
1 = SENSORS

4 = TEST

2 = PUMPS

5 = ALRM/EVT

3 = SYSTEM

6 = Q-START

4.10.0 Sensor Setup

Press the

PV/1 key at the Main Set Up menu display. Then press the ENTER key.

The

SENSOR SET UP MENU will be displayed as shown below:

AI 1 TYPE: $$$

SPAN= ### ZERO= ##

< OK $ (Y/N) >

To accept the current values, press

YES/7 key and then press the ENTER key.

To set up each field, press the

NO/0 key and then press the ENTER key.

The current

TYPE field starts blinking. Press the up (▲) and down (▼) keys to navigate to the desired TYPE

and then press the

ENTER key to confirm selection.

The following selections are valid:
SYS (System Pressure)
SUC (Suction Pressure)
RESYS (Redundant System Pressure)
FLOW (System Flow)
PRESS (For Monitor only)
NONE
If

RESYS is selected as a desired field, the following screen will get displayed:

ACTIVE SENSOR ##
DRIFT THRESHOLD ##%
DRIFT PR TM ###s
OK $ (Y/N)