Installation, Preinstallation, Pump location guidelines – Bell & Gossett DN0177 B Domestic Pump Centrifugal Pumps Series C35 User Manual

Page 12: Piping checklist, Pump location guidelines piping checklist

Advertising
background image

Installation

Preinstallation

Pump location guidelines

Follow these guidelines for locating the unit:

• Position the unit for easy access to all parts.
• Allow adequate space for servicing.
• Check ambient conditions.

Piping checklist

WARNING:
• The heating of water and other fluids causes volumetric expansion. The associated forces

can cause the failure of system components and the release of high-temperature fluids.
In order to prevent this, install properly sized and located compression tanks and
pressure-relief valves. Failure to follow these instructions can result in serious personal
injury or death, or property damage.

• Avoid serious personal injury and property damage. Make sure that the flange bolts are

adequately torqued.

• Never force piping to make a connection with a pump.

Check

Explanation/comment

Checked

Check that a section of straight pipe, with a length that

is five times its diameter, is installed between the

suction side of the pump and the first elbow, or that a

suction diffuser is installed.

This reduces suction turbulence by

straightening the flow of liquid before it enters

the pump.

Check that the suction and discharge pipes are

supported independently by use of pipe hangers near

the pump .

This eliminates pipe strain on the pump .

Check that there is a strong, rigid support for the

suction and discharge lines.

As a rule, ordinary wire or band hangers are not

adequate to maintain proper alignment.

For pumps with flanges, check that the bolt holes in

the pump flanges match the bolt holes in the pipe

flanges.

Check that the suction or discharge lines are not

forced into position.

Check that fittings for absorbing expansion are

installed in the system when considerable

temperature changes are expected.

This helps to avoid strain on the pump.

Check that a triple duty valve is installed in the

discharge line.

This valve serves as a check valve that protects

the pump from water hammer, and serves as

an isolation valve for servicing and for

throttling.

Check that the pipeline has isolation valves around

the pump and has a drain valve in the suction pipe.

Use PTFE tape sealer or a high quality thread sealant

when you install the suction and discharge

connections to a threaded pump housing.

Installation

10

Domestic

®

Pumps Centrifugal Pumps Series B35, C17, C35 Installation, Operation, and Maintenance Manual

Advertising