Technical data, Cable sizing/ratings – Xylem ADDEN600V R1 Aquavar CPC (Centrifugal Pump Control) 600 Volt Addendum User Manual

Page 2

Advertising
background image

2

TECHNICAL DATA

Cable Sizing/Ratings

500…600 Volt Drives
The following table provides Aquavar CPC rating information and
recommended wire sizing for the input and output cables.

CENTRIPRO AQUAVAR CPC

Input

NEMA 1

Cont.

NORMAL

Frame

Output

Input

Voltage Phase

Base

Output

DUTY

Size

2

Cable Size

Cable Size

Model

Amps

HORSEPOWER

Min. AWG

1

Min. AWG

1

CPC50031 2.7

2

R2

14

14

CPC50041 3.9

3

R2

14

14

CPC50061 6.1

5

R2

14

14

CPC50091 9

7.5

R2

14

14

CPC50111 11

10

R2

14

14

CPC50171 17

15

R2

14

14

CPC50221 22

20

R3

12

12

575 3

CPC50271 27

25

R3

10

10

CPC50321 32

30

R4

10

10

CPC50411 41

40

R4

8

8

CPC50521 52

50

R4

6

6

CPC50621 62

60

R4

6

6

CPC50771 77

75

R6

4

4

CPC50991 99

100

R6

3

3

CPC51251 125

125

R6

2

2

CPC51441 144

150

R6

1

1

(1) Recommended AWG Size based on NEC table 310.16, 40º C ambient, 90º C, UL type

copper wire. For other wire sizes or types, consult local or provincial codes.

(2) Terminal block for input voltage and output motor voltage have diameter limits. Consult technical section

(CABLE TERMINALS) for maximum wire diameter and torque values.

For submersible motor applications refer to motor manufacturers recommendations based on lead length and
voltage drop.

Advertising