Technical data, Fuse sizing/ratings – Xylem ADDEN600V R1 Aquavar CPC (Centrifugal Pump Control) 600 Volt Addendum User Manual
Page 3
3
TECHNICAL DATA
Fuse Sizing/Ratings
500…600 Volt Drives
The following table provides Aquavar CPC rating information and recommended fuse sizing
for the input short circuit protection. Branch circuit protection must be provided by the end
user, contractor or distributor. Sized according to local or applicable NEC codes.
CENTRIPRO AQUAVAR CPC
Input
NEMA 1
Cont.
NORMAL
Frame
Input
Fuse Type
3
Voltage Phase
Base
Output
DUTY
Size
Current UL Class T
Model
Amps
HORSEPOWER
Amps
CPC50031 2.7
2
R2
2.7
10
CPC50041 3.9
3
R2
3.9
10
CPC50061 6.1
5
R2
6.1
10
CPC50091 9
7.5
R2
9
15
CPC50111 11
10
R2
11
15
CPC50171 17
15
R2
17
25
CPC50221 22
20
R3
22
25
575 3
CPC50271 27
25
R3
27
40
CPC50321 32
30
R4
32
40
CPC50411 41
40
R4
41
50
CPC50521 52
50
R4
52
60
CPC50621 62
60
R4
62
80
CPC50771 77
75
R6
77
100
CPC50991 99
100
R6
99
150
CPC51251 125
125
R6
125
175
CPC51441 144
150
R6
144
200
(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type
JJS are shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse