Technical data, Fuse sizing/ratings – Xylem ADDEN600V R1 Aquavar CPC (Centrifugal Pump Control) 600 Volt Addendum User Manual

Page 3

Advertising
background image

3

TECHNICAL DATA

Fuse Sizing/Ratings

500…600 Volt Drives
The following table provides Aquavar CPC rating information and recommended fuse sizing
for the input short circuit protection. Branch circuit protection must be provided by the end
user, contractor or distributor. Sized according to local or applicable NEC codes.

CENTRIPRO AQUAVAR CPC

Input

NEMA 1

Cont.

NORMAL

Frame

Input

Fuse Type

3

Voltage Phase

Base

Output

DUTY

Size

Current UL Class T

Model

Amps

HORSEPOWER

Amps

CPC50031 2.7

2

R2

2.7

10

CPC50041 3.9

3

R2

3.9

10

CPC50061 6.1

5

R2

6.1

10

CPC50091 9

7.5

R2

9

15

CPC50111 11

10

R2

11

15

CPC50171 17

15

R2

17

25

CPC50221 22

20

R3

22

25

575 3

CPC50271 27

25

R3

27

40

CPC50321 32

30

R4

32

40

CPC50411 41

40

R4

41

50

CPC50521 52

50

R4

52

60

CPC50621 62

60

R4

62

80

CPC50771 77

75

R6

77

100

CPC50991 99

100

R6

99

150

CPC51251 125

125

R6

125

175

CPC51441 144

150

R6

144

200

(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type

JJS are shown in the Aquavar CPC tables. Other manufacturers are acceptable if they meet fuse
requirements.

Advertising