Xylem IM070 R03 Models 1GA/2GA User Manual
Page 16
 
14
1GA/2GA Installation, Operation and Maintenance Manual
NOTE: For safety reasons, the earth conductor should be approximately 2.0” (50 mm)
longer than the phase conductors. If the motor cable is jerked loose by mistake, the earth 
conductor should be the last conductor to come loose from its terminal. This applies to both 
ends of the cable.
Thermal contacts are incorporated in the stator. The thermal contacts can be connected to 
maximum 250 V, breaking current maximum 4 A. Goulds Water Technology recommends 
that they be connected to 24 V over separate fuses to protect the other automatic 
equipment.
Make sure that the pump is correctly earthed (grounded).
When using a variable-frequency-drive (VFD) special rules have to be followed to avoid 
clogging and over-heating. Contact your VFD supplier and ask for electrical limitations.
Remember that the starting current in direct online starting can be up to six times higher 
than the rated current. Make sure that the fuses or circuit breakers are of the proper rating.
The Parts List gives rated current. Fuse rating and cable shall be selected in accordance with 
local rules and regulations. Note that with long cables, the voltage drop in the cable must be 
taken into consideration, since the motor’s rated voltage is the voltage that is measured at 
the terminal board in the pump.
The overload protection (motor protection breaker) for direct online starting shall be set to
the motor rated current as given on the data plate.
Check the phase sequence in the mains with the phase sequence indicator.
If intermittent operation is prescribed (see Data Plate), the pump shall be provided with 
control equipment that provides such operation.
Single Phase Operation
The single phase pumps must be equipped with a starter which has start and run capacitors.
A special designed starter is required for the operation of single phase pumps. The 
connection of the motor cable to the starter is shown in the wiring diagram.
NOTE: It is not possible to change the direction of rotation of a single phase pump by
changing the cable conductors on the starter. Please contact your nearest Goulds Water 
Technology representative.
Monitoring Equipment
The FLS sensor consists of a small float switch for sensing water in the stator housing. Its 
design makes it suitable for pumps in vertical installations. The FLS sensor is installed in the 
bottom of the stator housing.
The MiniCas II is a monitoring relay to which FLS is connected.
Check:
• signals and tripping function.
• that relays, lamps, fuses and connections are intact.
Replace defective equipment.
Electrical Connections (continued)