GND Connection to Power Unit

(attached via the screws)

Section A

Troubleshooting the Control Card (using a Multimeter).

Power Supply disconnected!!!

The following tests have to be made without connected cables.

1) Internal Resistance – Digital Inputs:

Low Water
X3/1 (GND) – X3/11
=> 90k Ω / 2.5M Ω

External ON/OFF (release)
X3/1 (GND) – X3/7 => 14k Ω

Configurable Digital Input (Digi 1):
X3/1 (GND) – X3/9 => 14k Ω

Digital Inputs (Dig 2 /Dig 3 /Dig 4):
X3/1 (GND) – X3/5 / 6 / 15
=> 20k Ω

2) Internal Resistance of the Analogue

Current Inputs:

(Sensor 1/2 - Req. Val 1/2)

X3/1 (GND) – X3/2 / 4 / 18 / 23 =>50 Ω

3) Capacity of Electronic Ground to Earth:

X3/1 (GND) – earth => 60nF

Important to bleed off Hf- Disturbances!

Additional power supply ** max. 100 mA

Current signal input (required val. 2)
0-20mA / 4-20mA [Ri=50Ω]

Analog output 2 4-20mA [Ri=500Ω]
Analog output 1 0-10 VDC

Current signal input (required val. 1)
0-20mA / 4-20mA [Ri=50Ω]

Voltage signal input (required value 2)
0-10 VDC *DIG 4

Voltage signal input (required value 1)
0-10 VDC

Low water

Configurable digital input 1 DIG 1

External ON/OFF (release)

Actual-value-voltage input sensor 1 *DIG 2

Actual-value-voltage input sensor 2 *DIG 3

Actual-value-current input sensor 2
Sensor supply
** max. 100 mA
Actual value current input sensor 1
Ground

X3

X3

24 +24V

23

22

21

20

19 +10V

18

17

16
15

14

13

12

11

10

9

8

7

6

5

4
3 +24V

2

1