Check the following values:
Black Wire (GND)
Red Wire of Multimeter
Result
Rectifier Values
L1
L2
DC+
OL (Overload)
L3
L1
L2
DC–
0.40 - 0.54 V
L3
L1
DC+
L2
0.40 - 0.54 V
L3
L1
DC–
L2
OL (Overload)
L3
IGBT Values
U
DC+
V
0.420 - 0.635 V
W
U
DC–
V
OL (Overload)
W
U
V
DC+
OL (Overload)
W
U
V
DC-
0.40 - 0.45 V
W
NOTE: Put multimeter on diode check ( ).
Result:
- If the above mentioned values between power supply and DC part are significantly different
=> Rectifier may be damaged.
- If values between motor connection and DC part are significantly different
=> IGBT module may have a failure.