Xylem inc, Commercial water – Xylem IM224 R03 Hydrovar Variable Speed Control HV, 2HP-15HP Version 0307 User Manual

Page 7

Advertising
background image

Commercial Water

Xylem Inc.

PAGE 7

Check the following values:

Black Wire (GND)

Red Wire of Multimeter

Result

Rectifier Values

L1

L2

DC+

OL (Overload)

L3
L1
L2

DC–

0.40 - 0.54 V

L3

L1

DC+

L2

0.40 - 0.54 V

L3

L1

DC–

L2

OL (Overload)

L3

IGBT Values

U

DC+

V

0.420 - 0.635 V

W

U

DC–

V

OL (Overload)

W

U
V

DC+

OL (Overload)

W
U
V

DC-

0.40 - 0.45 V

W
NOTE: Put multimeter on diode check ( ).

Result:

- If the above mentioned values between power supply and DC part are significantly different

=> Rectifier may be damaged.

- If values between motor connection and DC part are significantly different

=> IGBT module may have a failure.