Xylem IM247 R02 SPD PLUS Centrifugal Pump Controller Quick Start Guide User Manual

Spd plus, Centrifugal pump controller quick start guide, Quickstart guide

Advertising
background image

SPD PLUS

Centrifugal Pump Controller

Quick Start Guide

Overview

The installation of the SPD PLUS adjust-able
speed drive follows the outline below.

Task

PREPARE for installation

UNPACK the drive

PREPARE mounting location

REMOVE the front cover

MOUNT the drive

INSTALL wiring

CHECK installation

REINSTALL the cover

APPLY power

START-UP Assistant

Application

This guide provides a quick reference for

installing SPD PLUS drives having a standard

enclosure (NEMA 1).
NOTE: This guide does not provide detailed

installation, safety or operational instruc-

tions. See the Installation Operation Manual

for complete information.

Prepare for Installation

WARNING! The Aquavar should ONLY
be installed by a qualified electrician.

Check

• Motor Compatibility – Motor type, nominal current,

frequency and voltage range must match drive

specifications (3 phase motor only).

• Suitable Environment – Drive requires heated,

indoor controlled environment that is suitable for

the selected enclosure below 122º F (50º C).

• Wiring – Follow local codes for wiring and fusing

requirements. Refer to NEC, Local, State or Munici-

pal codes.

Refer to the Installation Operation Manual and

confirm that all preparations are complete.

Tools Required

Screwdrivers, wire stripper, tape measure, mount-

ing screws or bolts, and drill.
Use the following chart to interpret the type code

found on the drive label.

Collect Motor Data

Collect the following data from the motor nameplate

for later use in the Aquavar startup:

• Voltage ______________________________
• Nominal Motor Current _______________
• Nominal Frequency ___________________
• Nominal Speed ______________________
• Nominal Power _______________________

Unpack the Drive

NOTE: Lift the SPD PLUS by its chassis and not
by its cover.

1. Unpack the drive.
2. Check for any damage and notify the

shipper immediately if damaged com-

ponents are found.

3. Check the contents against the order

and the shipping label to verify that all

parts have been received.

Prepare the Mounting Location

The drive requires a smooth,
vertical, solid surface, free from
heat and moisture, with free
space for air flow – 200 mm (8
in.) above and below, and 25
mm (1 in.) around the sides of
the drive.

1. Mark the mounting

points.

2. Drill the mounting holes.

Remove the Front Cover

1. Remove the control panel

(display), if attached.

2. Loosen the

captive screw
at
the top.

3. Pull near the

top to remove
the cover.

Mount the Drive

1. Position the

SPD PLUS and use
screws or bolts to
securely tighten all
four corners.

2. Attach a warning

sticker in the
appropriate lan-
guage on the inside
plastic shell.

Install the Wiring

(copper only)

1. Install thin-wall conduit clamps (not

supplied) in the conduit/gland box.

2. Install conduit/gland box.

Wiring Power

1. Connect conduit runs to box.
2. Route input power and motor

wiring through conduits.

1

X0002

SPD 4 0600 N1

Single Pump Drive

Voltage

2 – 230 Volt

4 – 460 Volt

5 – 575 Volt

Nominal Horsepower

0400 = 40 HP 0500 = 50 HP 0600 = 60 HP

0750 = 75 HP 1000 = 100 HP

Enclosure and Filter Options

Blank = NEMA 3R, no filter N1 = NEMA 1, no filter

F = NEMA 3R, with filter

NOTE: HP rating is for reference only, and is based on 3Ø input power.

3. Strip wires.
4. Connect power, motor and

ground wires to the drive terminals.

See “Power Supply and Wiring”

in the instruction manual.

Frame Sizes R1…R4

* Single phase input power must use U1, W1

and PE for wiring.

WARNING! For floating networks

remove screws at EM1 and EM3 on

Frame Sizes R1…R4.

Frame Size R5

Frame Size R6

WARNING!
For floating net-
works remove
screws at

F1 and F2
on Frame

Sizes R5 or R6.

QUICKSTART GUIDE

IM247R02