Wiring the Transducer

1. Route the

transducer

cable

through

the conduit.

2. Strip the

transducer

cable

sheathing

and twist

the screen

wire.

3. Connect the screen

wire of the

transducer to

terminal X1-1.

4. Connect the power supply wire of the

transducer (red or brown) to terminal

X1-10.

5. Connect analog output wire from the

transducer (white or black) to X1-5. See

chart in next column.

6. Install the conduit/gland box cover (1

screw).

1

Digital input impedance 1.5 kΩ. Maximum voltage

for digital inputs is 30 V.

Check Installation

Before applying power, perform the follow-
ing checks.

Check

Environment conforms to specifications.

The drive is mounted securely.

Proper cooling space around the drive.

Motor and driven equipment are ready for start.

Floating networks: Internal RFI filter disconnected.

Drive is properly grounded, with pump/motor.

Input power (mains) voltage matches the drive

nominal input voltage.

The input power (mains) terminals, U1, V1, W1,

are connected and tightened as specified.

The input power (mains) fuses / mains switch installed.

The motor terminals, U2, V2, W2, are connected

and tightened as specified.

Motor cable is routed away from other cables.

NO power factor compensation capacitors are

connected to the motor cable.

Control terminals are wired and tightened as specified.

NO tools or foreign objects (such as drill shavings) are

inside the drive.

NO alternate power source for the motor is connected

– no input voltage is applied to the output of the drive.

5

3

1

DIR

MENU

REM

11.1%

LOC

REM

40.2 PSI

sp

0.0 PSI

ac

0.0 HZ

Reinstall the Cover

1. Align the cover

and slide
it on.

2. Tighten

the captive
screw.

3. Reinstall the

control panel.

Apply Power

Always reinstall the front cover before turn-
ing power on.

WARNING! The SPD PLUS will start
up automatically at power up, if the
external run command is on.

1. Apply input power.

When power is applied to the SPD PLUS,
the green LED comes on.

NOTE! Before increasing motor speed,
check that the motor is running in the
desired direction.

Start-Up

Run the Start-Up Assistant

to configure the motor and

system parameters. If this is

the first time the drive has

been powered, the display

will prompt the user if they

would like to run the Start-

Up Assistant. Select Yes to

run the Start-Up Assistant.

If this is not the first time the drive has been

powered, follow the steps below:

1. From the Main Screen press MENU to

enter the MENU screen.

2. Select QUICKSTART

3. Select Start-Up

4. Follow the menu prompts to configure

the drive.

NOTE! For common parameters and

menu items, use the Help Key to

display descriptions. If you encounter

Alarms or Faults, use the Help Key or

refer to the Diagnostic section of the

instruction manual.