Refer to the status code label on the side of the controller access cover
to diagnose system errors. See the following diagram.

Red Flashes Fault Code

Restart Action

Constant

Replace Controller

Controller will not restart. Power must be reset to

clear the fault.

2 Blinks

No Water/Loss of Prime Controller will restart automatically according to

No Water Restart Time

the switches (switches 3 and 4 of bank 2).

3 Blinks

Sensor Fault

Controller will restart automatically when the sensor

signal is within the valid operating range.

4 Blinks

Pump or Motor Bound

Controller will restart automatically 5 times. After 5

faults the power must be reset to clear the fault.

5 Blinks

Short Circuit/

Controller will not restart. Power must be reset to

Ground Fault

clear the fault.

6 Blinks

Input Phase Loss

Controller will restart automatically 5 times. After 5

faults the power must be reset to clear the fault.

7 Blinks

Temperature

Controller will restart automatically when tempera

ture is within the operating range of the controller.

8 Blinks

Over Voltage

Controller will restart automatically when the input

voltage is within the operating range of the controller.

9 Blinks

Motor Overload

Controller will restart automatically.

QUICK START GUIDE

IMS-SDQ-2