ELECTRICAL CONNECTIONS

GROUNDING DIAGRAM

General Electrical Guidelines:

• Whenever possible avoid running control cables in

the same conduit with or bundled with AC power.

• Using shielded cable, be sure to connect shield to

ground at power supply end of the cable.

• Avoid routing flow sensor cables in close proximity to

a variable frequency drive.

• Recommended power and output wiring is shielded

twisted pair 18-22 AWG control cable.

• Recommended voltage is 12-24 Vdc. Note that

unregulated power supplies can vary from nameplate
voltage by a considerable amount, especially with AC
line voltage fluctuation. Therefore 24V power supplies
must be regulated.

See the Connections diagrams on the following pages for the
appropriate terminals.

Power:

A 12 - 24 Vdc power supply capable of at least 250

mA current output is needed.

Forward Flow Output:

This open-collector isolated output

does not supply power. This pulse is generated in the forward
flow direction on the standard unit. (Reverse flow output is
available as an option).

Note:

This output is limited to 6 mA at 30 Vdc maximum.

Reverse Flow Output:

Reverse flow output is available as

an option. This open-collector isolated output does not supply
power. It functions like a polarity-sensitive switch closure.
Note:

This output is limited to 6 mA at 30 Vdc maximum.

PLACE FERRITE BEAD HERE

Housing

Screw

Grounding Guidelines:

For best results, use a good quality earth ground, such as

metallic water piping or a driven ground, to ensure a good

connection to earth ground and good noise suppression.

If the flow sensor is installed in metallic piping, for optimum

connection clamp wire to the piping a short distance to one

side of the flow sensor using an electrical grounding clamp.

Connect the wire to the earth ground and to one of the housing

screws.

For Non-Metallic Pipe:

Connect one to the housing screws

by wire to a good earth ground, such as metalic water piping

or a rod driven into the ground.

EX meters are usually unaffected by moderate levels of electri-

cal noise. In some applications performance may be improved

by taking the following steps:

• Use shielded twisted pair cable (Belden 8723 or

equivalent above ground or Alpha 35482 or

equivalent burial).

• Clamp a ferrite bead (Steward 28A2029-OAO or

equivalent) on meter signal/power wire within 3/4”

of the meter strain relief (tape or tie wrap in place

if necessary). See diagram below.

• IMPORTANT - Connect the cable shield ground

wire to ground, ONLY at power supply end of cable.