General
Thank you for choosing ConTroller 712, the compact unit for
control of 2 pumps or valves with alternation and level alarm.

ConTroller 712 can be connected to a GSM / GPRS modem
for transmission of system conditions and alarms from the
pumping station to the SCADA system.

ConTroller 712 is DIN rail mounted, and is easy to install and
set up from the front panel.

Level measurement with electrodes
ConTroller 712 is measuring the level in the well by means of
base mounted or suspended level electrodes.

The mounting height of the electrodes determines the start and
stop levels for the pumps and the alarm level.

ConTroller 712 is equipped with 3 voltage free control relays, of
which 2 are used for control of 2 pumps/valve actuators, and
the remaining is alarm output.

Up to 5 level electrodes can be connected, of which 1
electrode is common/ground electrode.

Specifications

ConTroller 712

Dimensions:

86 x 105 x 60 mm (h x w x d)

Power supply:

230 V AC +/- 10 %

Consumption:

Approx. 5 VA

Temp. range:

- 10

… + 60 °C

Inputs:

4 x level electrodes and 1 x ground electrode

Udgange:

3 x voltage free changeover relays.
(Max. load 4 A resistive / 250 V AC)
Status signas to MJK GSM/GPRS modem.

Enclosure:

IP 22

Electrodes

With cable

For base

Base

Dimension:

6 x

6 x

60 x

130 mm

935 mm

71 mm

Advertising