Replacement Seal Instructions for
Close-Coupled and Base Mounted

Centrifugal Pumps

SAFETY

INSTRUCTIONS

This safety alert symbol will be used in this manual and on the

pump safety instruction decals to draw attention to safety

related instructions. When used the safety alert symbol means

ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED!

FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT IN A

SAFETY HAZARD.

NOTE: For additional information and instructions, refer to the

Installation Operation & Service Instructions Manual supplied

with your pump.

CLOSE-COUPLED PUMP

SERVICE INSTRUCTIONS

1.

2. Close valves on suction and discharge sides of pump. (If no

valves have been installed, it will be necessary to drain the

system.)

3.

4. Remove motor foot capscrews. Loosen volute capscrews, do

not remove them. Use capscrews in the jack screw holes.

Start to remove the pump assembly from the volute.

5. Remove seal flushing tube, if used. Remove the volute cap-

screws and remove the pump assembly from the volute.

6. Remove the impeller capscrews, lock washer and washer.

Remove the impeller.

7. Remove the rotating portion of the seal, use a screwdriver to

loosen the rubber ring.

8. Remove the seal insert along with the insert gasket and

retainer (if used).

9. Thoroughly clean the shaft sleeve and the coverplate seal

cavity. Inspect for surface damage like pitting, corrosion,

nicks or scratches. Replace if necessary.

10. Lubricate the shaft sleeve and coverplate seal cavity with

soapy water. (Do not use petroleum lubricant. ) Install a new

cup gasket and a new seal insert with indentation side down

into the cup.

11. Slide a new rotating seal assembly onto the shaft sleeve.

With a screwdriver push on the top of the compression ring

until the seal is tight against the seal insert. Install seal spring.

12. Install impeller, impeller washer. lock washer and capscrew,

then tighten capscrews (per torque chart).

13. Install new volute gasket then install pump assembly into

volute. Tighten volute capscrews (per torque chart). Install

seal flushing tube, if used. Install motor foot capscrews and

tighten. Install drain plug, close drain valve.

14. Open isolation valves, inspect pump for leaks, if not leaking

return pump to service.

WARNING: UNEXPECTED STARUP HAZARD

Disconnect and lock out power before servicing.

Failure to follow these instructions could result in serious

personal injury or death, or property damage.

CAUTION: EXTREME TEMPERATURE HAZARD

Allow pump temperature to reach acceptable levels

before proceeding. Open drain valve, do not proceed until

liquid stops coming out of drain valve. If liquid does not

stop flowing from drain valve, isolation valves are not seal-

ing and should be repaired before proceeding. After liquid

stops flowing from the drain valve, leave valves open and

continue. Remove the drain plug located on the bottom of

the pump housing. Do not reinstall plug or close drain valve

until re-assembly is completed.

Failure to follow these instructions could result in property

damage and/or moderate personal injury.

WARNING: EXCESSIVE PRESSURE HAZARD

Make certain internal pressure of the pump is relieved

before continuing.

Failure to follow these instructions could result in serious

personal injury or death, or property damage.