1.

2. Close valves on suction and discharge sides of pump. (If no

valves have been installed, it will be necessary to drain the

system.)

3.

4. Remove coupler guard and loosen set screws in both coupler

halves and slide each half back as far as possible on its shaft.

Remove coupler sleeve. Where a full diameter impeller is

used, it may be necessary to remove the pump side coupler

half and slide the motor back on its base in order to gain

sufficient clearance to remove the pump assembly from the

volute.

5. Remove support foot capscrews. Loosen volute capscrews,

do not remove them. Use capscrews in the jack screw holes.

Start to remove the pump assembly from the volute.

Remove seal flushing tube, if used.
Remove the volute capscrews and remove the pump assem-

bly from the volute.

6. Remove the impeller capscrews, lock washer and washer.

Remove th impeller.

7. Remove the rotating portion of the seal, use a screwdriver to

loosen the rubber ring.

8. Remove the seal insert along with the insert gasket and

retainer (if used).

9. Thoroughly clean the shaft sleeve and the coverplate seal

cavity. Inspect for surface damage like pitting, corrosion,

nicks or scratches. Replace if necessary.

10. Lubricate the shaft sleeve and coverplate seal cavity with

soapy water. (Do not use petroleum lubricant.) Install a new

cup gasket and a new seal insert with indentation side down

into the cup.

11. Slide a new rotating seal assembly onto the shaft sleeve.

With a screwdriver push on the top of the compression ring

until the seal is tight against the seal insert. Install seal spring.

12. Install impeller, impeller washer, lock washer and capscrew,

then tighten capscrews (per torque chart).

13. Install new volute gasket then install pump assembly into

volute. Tighten volute capscrews (per torque chart). Install

seal flushing tube, if used. Install motor foot capscrews and

tighten. Install drain plug, close drain valve.

14. Open isolation valves, inspect pump for leaks, if not leaking

return pump to service.

WARNING: UNEXPECTED STARUP HAZARD

Disconnect and lock out power before servicing.

Failure to follow these instructions could result in serious

personal injury or death, or property damage.

CAUTION: EXTREME TEMPERATURE HAZARD

Allow pump temperature to reach acceptable levels

before proceeding. Open drain valve, do not proceed until

liquid stops coming out of drain valve. If liquid does not

stop flowing from drain valve, isolation valves are not seal-

ing and should be repaired before proceeding. After liquid

stops flowing from the drain valve, leave valves open and

continue. Remove the drain plug located on the bottom of

the pump housing. Do not reinstall plug or close drain valve

until re-assembly is completed.

Failure to follow these instructions could result in property

damage and/or moderate personal injury.

Capscrew

Head

Capscrew Diameter

Type

Marking

1

/

4

5

/

16

3

/

8

7

/

16

1

/

2

5

/

8

3

/

4

7

/

8

1

SAE Grade 2

6

13

25

38

60

120

190

210

300

Brass

4

10

17

27

42

83

130

200

300

Stainless Steel

or

SAE Grade 5

10

20

35

60

90

180

325

525

800

CAPSCREW TORQUE (FOOT-POUND)

STANDARD MECHANICAL SEAL CONSTRUCTION

BASE-MOUNTED PUMP

NOTE: For additional information and instructions, refer to the

Installation Operation & Service Instructions Manual supplied with

your pump.

WARNING: EXCESSIVE PRESSURE HAZARD

Make certain internal pressure of the pump is relieved

before continuing.

Failure to follow these instructions could result in serious

personal injury or death, or property damage.