From the Technologic Pump Controller screen,
shown in section 3.2, press the SETUP/3 key to get
to the Setup Selection Menu shown below.
Setup Selection: 0
1 = Sensors 4 = Test
2 = Pumps 5 = Default
3 = System 0 = Exit
Press the NEXT SCREEN key to view the neighboring
page, which is shown below. Press PREV. SCREEN
to return to the screen shown above.
Setup Selection: 0
6 = Chillers
7 = Bypass Valve
0 = Exit
Press the numeric key that corresponds to the
desired Setup Menu and then press ENTER.
4.1
Sensors
From the Setup Selection Menu, shown in section 4,
press PROCESS VARIABLE/1 and ENTER, to get to
the Sensors screens.
4.1.1
Sensor Number
The first of the Sensors screens is the Sensor Number
screen. The display will show:
Sensor No: #
Press the numeric key(s) for the sensor you wish to
setup. The sensor number is limited to the maximum
number of sensors allowed, typically 16. Press the
ENTER key to proceed.
4.1.2
Edit/Copy
After entering the sensor number, the display will show:
Sensor No: #
1 - Edit 2 - Copy : #
0 - Exit
Press PROCESS VARIABLE/1 and then the ENTER
key to edit the sensor setup. See section 4.1.3.
Press SET POINT/2 and then the ENTER key to copy
from an existing sensor. See section 4.1.13.
4.1.3
Sensor Edit
If 1-Edit was selected in section 4.1.2, the display will
show:
Sensor No ##
(Type)
Span = 0
Zero = 0
*PV:Y/N
*Set Point No: #
*Override:Y/N
Ok ? (Y/N)
*PV, Set Point No, and Override will only appear if
the sensor was previously set up to be a process
variable.
Press YES/7 and then ENTER to accept these values,
and proceed to section 4.1.4. Press NO/0 and
ENTER to modify these values, and skip to section
4.1.5.
4.1.4
Do Another
If YES/7 was selected in the Sensor Edit Menu,
shown in section 4.1.3, the display will show:
DO ANOTHER ? (Y/N)
Press YES/7 and then ENTER to set up another sen
-
sor, or press NO/0 and ENTER to return to the Setup
Selection Menu shown in section 4.
4.1.5
Sensor Type
If NO/0 was selected in the Sensor Edit Menu, shown
in section 4.1.3, the following is displayed:
No: ##
Sensor Type: #
1 = DP, 2 = PR, 3 = Flow
4=KW, 5 = Temp, 6 = DT
7 = SyDp, 8 = SyKW, 0 = None
To view the neighboring screen, Press the NEXT
SCREEN key. The following will be displayed:
No: ##
Sensor Type: #
9 = Chi Flow, 10 = Chi DP
11=S Temp, 12 = R Temp
13 = Bep V Fb, 0 = None
Table 2, shown on next page, gives a description and
the units of each sensor type.
Enter the numeric key followed by ENTER for the
type of sensor you are setting up. The abbreviation
for the sensor type will appear in the upper right cor-
ner of the display in the following screens.
*If the sensor type is Chi Flow or Chi DP, then see
section 4.1.14.
4.1.6
Sensor Span
The display will now show the selected sensor type
and prompt the user for the sensor span as shown
below.
Sensor No ## (Type)
Span = #####
Obtain the span of the sensor from the nameplate on
the sensor. Enter the span by pressing the appropri-
ate numeric keys followed by the ENTER key.
4.1.7
Sensor Zero
The display will now prompt the user for the zero of
the sensor as follows:
Sensor No ## (Type)
Span = ##### Zero = #####
12
Section 4 - Setup Selection Menu