From the Technologic Pump Controller screen,

shown in section 3.2, press the SETUP/3 key to get
to the Setup Selection Menu shown below.

Setup Selection: 0

1 = Sensors 4 = Test
2 = Pumps 5 = Default
3 = System 0 = Exit

Press the NEXT SCREEN key to view the neighboring

page, which is shown below. Press PREV. SCREEN
to return to the screen shown above.

Setup Selection: 0

6 = Chillers
7 = Bypass Valve
0 = Exit

Press the numeric key that corresponds to the

desired Setup Menu and then press ENTER.

4.1

Sensors

From the Setup Selection Menu, shown in section 4,

press PROCESS VARIABLE/1 and ENTER, to get to
the Sensors screens.

4.1.1

Sensor Number

The first of the Sensors screens is the Sensor Number

screen. The display will show:

Sensor No: #

Press the numeric key(s) for the sensor you wish to

setup. The sensor number is limited to the maximum
number of sensors allowed, typically 16. Press the
ENTER key to proceed.

4.1.2

Edit/Copy

After entering the sensor number, the display will show:

Sensor No: #

1 - Edit 2 - Copy : #

0 - Exit

Press PROCESS VARIABLE/1 and then the ENTER

key to edit the sensor setup. See section 4.1.3.

Press SET POINT/2 and then the ENTER key to copy
from an existing sensor. See section 4.1.13.

4.1.3

Sensor Edit

If 1-Edit was selected in section 4.1.2, the display will

show:

Sensor No ##

(Type)

Span = 0

Zero = 0

*PV:Y/N

*Set Point No: #

*Override:Y/N

Ok ? (Y/N)

*PV, Set Point No, and Override will only appear if

the sensor was previously set up to be a process
variable.

Press YES/7 and then ENTER to accept these values,
and proceed to section 4.1.4. Press NO/0 and
ENTER to modify these values, and skip to section
4.1.5.

4.1.4

Do Another

If YES/7 was selected in the Sensor Edit Menu,

shown in section 4.1.3, the display will show:

DO ANOTHER ? (Y/N)

Press YES/7 and then ENTER to set up another sen

-

sor, or press NO/0 and ENTER to return to the Setup
Selection Menu shown in section 4.

4.1.5

Sensor Type

If NO/0 was selected in the Sensor Edit Menu, shown

in section 4.1.3, the following is displayed:

No: ##

Sensor Type: #

1 = DP, 2 = PR, 3 = Flow
4=KW, 5 = Temp, 6 = DT
7 = SyDp, 8 = SyKW, 0 = None

To view the neighboring screen, Press the NEXT

SCREEN key. The following will be displayed:

No: ##

Sensor Type: #

9 = Chi Flow, 10 = Chi DP
11=S Temp, 12 = R Temp
13 = Bep V Fb, 0 = None

Table 2, shown on next page, gives a description and

the units of each sensor type.

Enter the numeric key followed by ENTER for the
type of sensor you are setting up. The abbreviation
for the sensor type will appear in the upper right cor-
ner of the display in the following screens.

*If the sensor type is Chi Flow or Chi DP, then see
section 4.1.14.

4.1.6

Sensor Span

The display will now show the selected sensor type

and prompt the user for the sensor span as shown
below.

Sensor No ## (Type)

Span = #####

Obtain the span of the sensor from the nameplate on

the sensor. Enter the span by pressing the appropri-
ate numeric keys followed by the ENTER key.

4.1.7

Sensor Zero

The display will now prompt the user for the zero of

the sensor as follows:

Sensor No ## (Type)

Span = ##### Zero = #####

12