Section 5 - Operation

5.1

Status Screens

5.1.1

Technologic Pump Controller Screen

The Technologic Pump Controller screen displays the

date, time, status, and mode of operation. STATUS
indicates the current alarm status. If NORMAL is dis-
played, there are no alarms. If *ALARM* is displayed,
there are alarms that may prevent normal operation.
See section 5.11 for more information on alarms.

MODE, in the lower right corner, will display the sys-
tem operation mode. The operation mode will be Auto,
Manual or Manual Bypass. See sections 5.5-5.7.

Technologic Pump

Controller

MM/DD/YY HH:MM:SS

STATUS MODE

During normal operation, PREV. SCREEN and NEXT

SCREEN can be pressed to scroll through the status
screens shown below.

5.1.2

Pump Status Screen

Pressing NEXT SCREEN, the controller will display

the Pump Status screen shown below.

Pump Status

P1:*

P2:*

P3:*

P4:*

P5:*

P6:*

STATUS

MODE

*The pump status will be displayed for each defined

pump. The valid options are as follows:

N/A = Pump not available as defined by setup.
Rdy = Pump available, not running.
On = Pump is running.
Off = Pump disabled, will not be allowed to start.

5.1.3

Pump Speed Screen

Pressing NEXT SCREEN, the controller will display

the Pump Speed screen shown below.

Pump Speed %

P1: 0

P2: 0

P3: 0

P4: 0

P5: 0

P6: 0

STATUS

MODE

The actual pump speed is shown. Allowable values

are 0-100%.

5.1.4

Chiller Status Screen

Pressing NEXT SCREEN, the controller will display

the Chiller Status screen shown below.

Chiller Status

C1:*

C2:*

C3:*

C4:*

C5:*

C6:*

STATUS

MODE

*The chiller status will be displayed for each defined

chiller. The possible states are as shown below.

N/A = Chiller not available as defined by setup.
Rdy = Chiller available, not running.
On = Chiller is running. (Received Chiller “Start” DI.)
Off = Chiller disabled, will not be allowed to start.

5.1.5

Chiller Data Screen

Pressing NEXT SCREEN, the controller will display

the Chiller Data screen shown below.

Chiller Data (UNITS)

C1: 0 C4: 0
C2: 0 C5: 0
C3: 0 C6: 0

If the chiller flow is monitored by a flow meter the

units are GPM.

If the chiller flow is monitored by a Differential Pres-
sure meter the units are PSI.

5.1.6

Active Values Data Screen

Pressing NEXT SCREEN, the controller will display

the Active Values Data screen shown below.

Active Values

Zone: ###

Flow: ###

KW: N/A

SysDp: N/A

STATUS

MODE

The actual values for each signal are displayed.

5.1.7

Bypass Valve Signal Screen

Pressing NEXT SCREEN, the controller will display

the Bypass Valve Signal screen shown below.

Bypass Valve

Signal To Valve ###%
Signal Frm Valve n/a
Valve Control Man

The analog signal (4 - 20mA or 0-10V) to and from

the valve is displayed, in percentage.

5.1.8

Manual Speed Screen

Pressing NEXT SCREEN, the controller will display

the Manual Speed screen, shown below. This screen
will only be present if the operation mode is Manual.

Manual Speed ###%

STATUS MODE

Press F2/6, the up arrow, to increase the pump

speed. Press F4/9, the down arrow, to decrease pump
speed.