System Connections

Connect the Lowara Servitec system inlet port (marked 1) to the return leg of the circulating
system maximum temperature 70˚C, connect the system outlet port (marked 2) down stream of
the inlet port, minimum distance 500mm The connections to the main pipe should be made at the
top or side of the pipe not the bottom, this is to prevent dirt being transferred to the Servitec.

3

t500

Main current V
circuit water

t500

Main current V
circuit water

Rich in
gas

Low in
gas

Rich in
gas

Low in
gas

From above

From below as an
immersion tube

Butt-welded from the
bottom not permitted

t

5

00

Rich in
gas

Low in
gas

At the side

(horizontal and vertical
assembly possible)

M

ain current

V

circuit water

Make up water

Make up water is generally provided by a separate pressurisation unit placed in the system and
will work independently of the Lowara Servitec unit. In this case the water make up (port 3) can be
blanked off and not used. It is possible to connect a basic fill unit to the system for water make
which can be controlled by the Servitec unit, in this case the fill unit outlet should be connected the
Servitec make up port (Marked 3) maximum pressure 6 bar. The appropriate electrical connections

will also need to be made.

Initial start up

1.

Check that the electrical connections are all made in accordance with local bylaws.

2.

Check that the system connections have been made and the isolation valves are open.

3.

Check that the pipe lines to the Servitec have been cleaned and are clear of any debris that
may have accumulated during installation.

Parameter Settings
The Lowara Servitec has two parameter setting levels, one is for service use and is password protected, and the
second is for customer use and is not protected.
During initial start up the customer parameters must be set to the system specific conditions.