Caution, Diagram 1 diagram 2, Diagram 3 – Xylem MM 200G Series 64 Low water Cut-Offs User Manual

Page 7: Cover switch housing

Advertising
background image

7

0

2

0

4

1

0

3

0

0

2

0

4

1

0

3

0

0

2

0

4

1

0

3

0

SCHEMATIC OF TWIN SWITCH

INTERNAL OPERATION

NORMAL WATER LEVEL

FEEDER OR ALARM
OPERATING LEVEL

LOW WATER CUT-OFF
OPERATING LEVEL

NEUTRAL WIRE

NEUTRAL WIRE

HOT WIRE

HOT WIRE

TO BURNER

TO ALARM

SAFETY
SWITCH

0

2

0

4

1

0

3

0

USED AS MAIN LINE SWITCH

Diagram 1

Diagram 2

NEUTRAL WIRE

TO

TWO WIRES OF 101A

OR TO ALARM CIRCUIT

HOT WIRE

TO BURNER

JUMPER

SAFETY
SWITCH

0

2

0

4

1

0

3

0

USED WITH MODEL 101 ELECTRIC

WATER VALVE OR IN ALARM CIRCUIT

Diagram 3

WIRING SCHEMATIC

SWITCH SCHEMATIC

IMPORTANT: Low water cut-off circuit of the 64 series must be electrically wired in series with all other boiler
limit operating controls.

Cover

Switch

Housing

Place the cover on the switch housing and, using
a flathead screwdriver, tighten the one (1) screw
to approximately 2 ft•lb (2.6 N•m).

1

2

3

4

NEUTRAL

HOT

ALARM

RESET

BUTTON

BURNER

TRANSFORMER

(OPTIONAL)

Model 64A-M For use on 24 or 120 VAC systems requiring manual reset on low water cut-off.

Do not electrically connect water feeder to Model 64A-M. This

model includes a manual reset feature, failure to follow this

caution could result in boiler flooding and property damage.

CAUTION

NORMAL WATER LEVEL

1

2

3

4

RESET

BUTTON

1

2

3

4

RESET

BUTTON

LOW WATER CUT-OFF
ALARM LEVEL