Troubleshooting testing – Xylem MM 206F Series 63 Low Water Cut-Off User Manual

Page 6

Advertising
background image

6

TROUBLESHOOTING

TESTING

Problem:

1. Burner does not shut off on low water.

a. Cause: Float chamber is loaded with mud or

sediment.

Test: With water level below the control

check if terminals C and N.C. are open.
If not, remove switch and manually test
if terminals C and N.C. can be opened.

Solution: Open float chamber and clean. At this

time, check for a build-up of scale or
sediment between corrugations of the
bellows.

b. Cause: Contacts are fused together.

Test: Remove switch and operate manually to

verify proper switch operation.

Solution: Replace switch. Check electrical load

and make sure it is within the ratings
of the switch.

CUT OFF

LEVEL

TEST
OPENING

• Control can be tested on a hot water

boiler by gently inserting a screwdriver
or similar tool in the test opening below
the switch (see drawing) and lifting linkage
to cause float to drop, thereby simulating a
low water condition.