Wiring diagrams – Xylem MM 219J Replacement Head Mechanism User Manual

Page 9

Advertising
background image

9

WIRING DIAGRAMS

For Motorized Valves, refer to the valve manufacturer's wiring instructions.

Pump Control Only

1. Install a starter or relay in pump control circuit,

as shown, to prevent damage to snap switch
and help insure proper switch/control operation.
Failure to do so may shorten the life of the switch
when actual amperage exceeds switch rating.

2. Connect wires from holding coil of pump starter

or relay to terminals 1 and 2 as shown.

1. Main Line Switch - For burner circuits within

the switch’s electrical rating.

2. Pilot Switch - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.

1 2

4 5 6

ALARM

NEUTRAL

HOT

ALARM

NEUTRAL

HOT

1 2

4 5 6

1 2

4 5 6

SEE PUMP

CONTROL

CIRCUIT

TO NEUTRAL

TO BURNER CONTROL CIRCUIT

HOT

ALARM

1 2

4 5 6

LOAD

LINE (3 PHASE)

SEE PUMP

CONTROL

CIRCUIT

ALARM

1 2

4 5 6

LOAD

LINE

OR

OR

Combination Pump Control, Low Water Cut-Off and Alarm

Alarm Circuit Only

1. Low Water Alarm

2. High Water Alarm

NOTE

To help insure most effective operation,
balance boiler feed pump(s) to deliver
required water feed rate to match boiler
steaming requirements.

NOTE

For Model 159S, use terminals 5 and 6 from
starter or relay for pump #2.

Low Water Cut-Off Only

1. Main Line Switch - For burner circuits within the

switch’s electrical rating.

LINE

LOAD

1 2

4 5 6

1 2

4 5 6

LOAD

LINE

OR

2. Pilot Switch - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.