PUMP
SWITCH

PUMP
SET SCREW

N

PUMP OFF
PUMP ON

BURNER
“CUT-OFF LEVEL”
AT CAST LINE

10

ADD ADHESIVE HERE

O

5b. If the Pump Off point does not match the one shown in chart for the

control (pages 3 and 4) and as measured on the "Switching Level
Ruler", dig the inspection lacquer out of the socket in the set screw
(N) above the pump switch in the actuator assembly using an awl.

c. Using an Allen wrench with a 5/64" hex, turn the screw 1/4 turn:

- clockwise (if the “Pump Off” point is too

high when viewed from top)

- counterclockwise (if the “Pump Off” point

is too low when viewed from top)

5d. Slowly drain the water in the boiler until the pump turns on.

Allow pump to fill the boiler and observe the point on the ruler
where the water level shuts off.

5e. Repeat steps 5a. through d. as necessary to match the

specified Pump Off point specification.

f.

Apply one drop of adhesive (furnished) to the set screw threads
(O) above the pump switch in the actuator assembly.

PUMP OFF
PUMP ON

BURNER
“CUT-OFF LEVEL”
AT CAST LINE

5a. Slowly drain the water in the boiler until the

pump turns on. Allow pump to fill the boiler
and observe the point on the ruler where the
water level shuts off.

5 - Setting the Operating Points of the Pump Switch

IMPORTANT: Where Pump On/Off and Burner On/Off are referenced in these instructions, Pump #1 On/Off
and Pump #2 Off/On should be substituted, respectively, for a 159S control, and Motorized Valve
Open/Closed can substitute for Pump On/Off for a 158S control.