Installation, Warning, Terminal connection reference chart – Xylem MM 235E Replacement Snap Switch Assembly SWA 150S 150S MD 158S 159S User Manual

Page 6

Advertising
background image

PUMP
SWITCH

PUMP

CIRCUIT

TERMINALS

LOW WATER
CUT-OFF AND
ALARM SWITCH

ALARM

CIRCUIT

TERMINALS

LOW WATER

CUT-OFF

TERMINALS

6

3. Remove the cover (B).

4. Mark and remove the pump switch and

burner/alarm switch wires from terminal block.

1. Turn the boiler off.

A

2. Allow the boiler to cool to 80˚F (27˚C) and

release the boiler pressure to 0 psi (0 bar).
Drain water in the boiler to a level which is
below the float chamber (A).

INSTALLATION

SECTION 1 - Switch Bracket Replacement

• To prevent electrical shock, turn off the electrical power before making electrical connections.

• This low water cut-off must be installed in series with all other limit and operating controls installed on the

boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving
the site.

Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in
property damage, personal injury or death.

!

WARNING

B

OFF

ON

Terminal Connection

Product

Switch

1

2

3

4

5

6

150S/157S

2 Wire

Blue

Yellow

Pump

3 Wire

Black

White

Red

Burner

158S

3 Wire

Black

White

Red

Pump

3 Wire

Black

White

Red

Burner

159S

2 Wire

Blue

Yellow

Pump

2 Wire

Blue

Yellow

Burner

Terminal Connection Reference Chart