INSTRUCTION MANUAL

MM-243D

2

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Pump Off

1

3

/

8

(35)

3

/

4

(19)

Pump On

5

/

8

(16)

Burner On

7

/

8

(22)

7

/

8

(22)

Burner Off

0

(0)

NORMAL BOILER

WATER LINE

PUMP

OFF

BURNER

OFF

BURNER

“CUT-OFF LEVEL”

AT CAST LINE

1 3/8" (35mm)

CUT-OFF

LEVEL

NORMAL BOILER

WATER LINE

CUT-OFF

LEVEL

PUMP OFF
PUMP ON

3/4" (19mm)

OPERATION

Maximum Pressure: 50 psi (3.5 kg/cm

2

)

Electrical Ratings

Settings and Differential Pressures

Values are ± 8” (3.2mm).

Series 42S

50 psi

(3.5 kg/

cm

2

)

Pressure

Pump Circuit Rating (Amperes)

Voltage

Full Load

Locked Rotor

Pilot Duty

120 VAC

7.4

44.4

345 VA at

240 VAC

3.7

22.2

120 or 240 VAC

NORMAL BOILER

WATER LINE

BURNER

CUT-OFF LEVEL

AT CAST LINE

7/8" (22 mm)

BURNER ON
BURNER OFF

CUT-OFF

LEVEL

Motor Horsepower

Voltage

Hp

120 VAC

1/3

240 VAC

1/3

• Before using this product read and understand instructions.

• Save these instructions for future reference.

• All work must be performed by qualified personnel trained in the proper application, instal-

lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.

• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be

0 psi (0 bar) before servicing.

• To prevent electrical shock, turn off the electrical power before making electrical connections.

• This low water cut-off must be installed in series with all other limit and operating controls

installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.

• To prevent serious personal injury from steam blow down, connect a drain pipe to the

control opening to avoid exposure to steam discharge.

• To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at

120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.

Failure to follow this warning could cause property damage, personal injury or death.

WAR

NING

CAUT

ION

!

WARNING

Replacement Head Mechanism

Replacement head mechanisms can be installed without
disturbing existing equalizing connections or disassembly
of components, making repairs simple and easy.

Replacement Head Mechanism

42S-HD

(Snap Switch)