Specifications, Operation, Control unit temperature ratings – Xylem MM 284D Series PSE-800 Probe Type Low Water Cut-Off for Steam Boilers User Manual

Page 2: Probe specifications

Advertising
background image

2

SPECIFICATIONS

Model

Control Voltage Motor Switch Rating

Pilot Rating

PSE-802-24
PSE-802-U-24

24 VAC

N/A

50VA

PSE-802-RX2-24
PSE-801-120

120 VAC

7.5 FLA 43.2 LRA

125VA

PSE-801-U-120

The Series PSE-800 probe type LWCO’s provide
protection against low water conditions for residential
and commercial steam boiler applications. The control
uses patented technology to monitor changes in
water conductivity. When defined parameters are
exceeded, the new PSE-800 makes a decision to
shut the burner off based on the volatility/variability

of the resistance readings. This new patented technology
provides the best protection possible without turning
off the boiler unless a low water condition exists. As
an added measure of safety, the control will turn off
the boiler if it recognizes an out-of-water condition
when the sensitivity threshold is exceeded.

Green

(Power On)

Red

(Low Water)

Operation

Automatic reset after power outage

All models include a provision for adding an alarm or automatic
water feeder.

30 second Delay on Make (DOM)

10 second Delay on Break (DOB)

Control Unit
Temperature Ratings:

Temperature:

Storage: -40˚F to 135˚F (-40˚C to 57˚C)

Ambient: 32 F to 120 F (0 C to 4 C)

Humidity: 85% (non-condensing)

Probe Specifications

Maximum Steam Pressure: 15 psi (1.0 kg/cm

2

)

Probe Sensitivity: 7,000 ohm

HZ: 50/60

Control Power Consumption:

1.7VA @ 24VAC

3.6VA @ 120VAC

Electrical Enclosure Rating: NEMA 1 General Purpose

o

o

o

o

9