STEP 4 - Control Wiring (continued)

N

P

M

d. For all wire connections to the terminal block (M).

1.Strip about 1/3" (8.5 mm) of insulation from the wire.
2.Loosen the terminal screw (N) but DO NOT

REMOVE. Move the wire clamping plate (P) back until the
plate touches the back side of the screw head.

3.Insert the stripped end of the wire under the wire clamping

plate (P) and securely tighten the terminal screw (N).

INSTALLATION COMPLETE

E

H

N

H

C

W

B

BURNER

CIRCUIT

C

B

D

A

N

120 VOLT

CIRCUIT

• Connect Hot wire (A) of 120 volt circuit to terminal (H).

• Connect Neutral wire (B) of 120 volt circuit to terminal (N).

• Connect wire (C) from beginning of Burner circuit (thermostat,

gas valve, limits, etc.) to terminal (B).

• Connect wire (D) from end of Burner circuit to terminal (N).

• Connect jumper wire (E) to terminals (H) and (C).

PSE-801 with 120 Volt Burner Circuit

E

H

N

H

C

W

B

BURNER

CIRCUIT

E

C

B

A

N

120 VOLT

CIRCUIT

L

1

L

2

T

1

T

2

24 VOLT

TRANSFORMER

(BY OTHERS)

D

• Connect hot wire (A) of 120 volt circuit to terminal (H) and

transformer terminal (L1).

• Connect neutral wire ‘B’ of 120 volt circuit to terminal (N) and

transformer terminal (L2).

• Connect wire (C) from beginning of Burner circuit

(thermostat, gas valve, limits, etc.) to terminal (B).

• Connect wire (D) from end of Burner circuit to transformer

terminal (T2).

• Connect wire (E) from transformer terminal (T1) to

terminal (C).

PSE-801 with 24 Volt Burner Circuit

A

B

Wiring harness is provided by boiler manufacturer.

NOTE

Do not use force to insert plug. This may damage
receptacle solder connections.

!

CAUTION

Connect plug (A) of wiring harness to receptacle (B).

Check to make sure factory supplied jumper is installed
between terminals (H) and (C).

PSE-802 using Harness Connection

PSE-802 using Terminal Connections

D

N

H

C

W

B

BURNER

CIRCUIT

C

B

A

24 VOLT
POWER

CIRCUIT

JUMPER
BAR

N H

B

• Connect neutral wire (A) of 24 volt circuit to terminal (N).

• Connect hot wire (B) of 24 volt circuit to terminal (H).

• Connect wire (C) from beginning of Burner circuit

(thermostat, gas valve, limits, etc.) to terminal (B).

• Connect wire (D) from end of Burner circuit to terminal (N).

• Make sure factory provided jumper bar is connected to

terminal (H) and (C).