Xylem MM 307H Series 101-A Electric Water Feeder User Manual

Series 101-a electric water feeder, Warning, Specifications

Advertising
background image

INSTRUCTION MANUAL

Series 101-A
Electric Water Feeder

Applications:

For use on low pressure boilers with cold water

feed. The Series 101-A can be used with mechanical

or electronic low water cut-off controls.

with

QUICK

CHANGE

Cartridge

• Before using this product read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, instal-

lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.

• Boiler manufacturer schematics should always be followed. In the event that the boiler

manufacturer’s schematic does not exist, or is not available from the boiler manufacturer,
refer to the schematics provided in this document.

• To prevent water damage check to make sure there is adequate floor drainage capacity.

Check all components in the system to insure that they will not leak in the event of an
overfeed condition.

• To prevent electrical shock, turn off the electrical power before making electrical connections.

WARNING

CAUTION

!

WARNING

Do not use automatic water feeders with manual reset LWCO’s.
Failure to follow this warning could cause flooding, property dam-

age, personal injury or death.

!

WARNING

SPECIFICATIONS

Maximum Water Pressure:

150 psi (10.5 kg/cm

2

)

Maximum Boiler Pressure:

25 psi (1.76 kg/cm

2

)

Maximum Boiler Size:

5000 sq. ft. EDR

2,350,000 BTU/HR

Output Capacity

Flow Data

Pressure Differential

Flow Rate

psi (kg/cm

2

)

gpm (lpm)

5

(.4)

1.4

(5.3)

10

(.7)

1.7

(6.4)

20

(1.4)

2.1

(7.9)

40

(2.8)

2.9

(11.0)

60

(4.2)

3.4

(12.9)

80

(5.6)

4.0

(15.1)

Electrical Ratings

Model

Voltage

Full Load

101A-120

120V

40 VA

101A-24

24V

40 VA

NOTE:

101A-24 includes a transformer with

120 volt primary and 24 volt/50VA secondary.

MM-307H

California Proposition 65 warning! This product contains chemicals known to the

state of California to cause cancer and birth defects or other reproductive harm.

Previous controls should never be installed on a new system. Always install new

controls on a new boiler or system.

CAUTION:

A more frequent replacement interval may be necessary based on the condition of

the unit at time of inspection. McDonnell Miller s warranty is one (1) year from date

of installation or two (2) years from the date of manufacture.

Failure to follow this warning could cause property damage, personal inj ury or death.

!

&

'