6

1

2

3

4

5

101A

WATER

FEEDER

HOT NEUTRAL

120 VAC SUPPLY

JUMPER

B

A

PS-801-120

LOW WATER CUT-OFF

BURNER

CIRCUIT

For Model 101A-120 Water Feeder and Model PS-801-120 Low Water Cut-Off

h.

Install wire (A) from the water feeder to terminal 2
on the low water cut-off.

i.

Install wire (B) from the water feeder to terminal 4
on the low water cut-off.

Reinstall electrical cover plate.

24V TRANSFORMER
(101-24 V-48)

N

H

C

W

B

BURNER

HOT

NEUTRAL

120 VAC SUPPLY

JUMPER BAR

A

B

101A-24

WATER FEEDER

PS-802-24 LOW WATER CUT-OFF

For Model 101A-24 Water Feeder and Model PS-802-24 Low Water Cut-Off

Replace existing 24 volt transformer on boiler with the
McDonnell and Miller transformer Model 101-24 V-48
included with the Model 101A-24 water feeder.

h.

Install wire (A) from the water feeder to terminal N
on the low water cut-off.

i.

Install wire (B) from the water feeder to terminal W
on the low water cut-off.

j.

Install jumper bar or wire from terminal H to terminal
C on the low water cut-off.

To prevent damage to the water feeder, a McDonnell
& Miller transformer Model 101-24V-48 must be used.

!

IMPORTANT