MAINTENANCE

SCHEDULE:

Weekly
• Blow down when boiler is in operation.

Annually
• Disassemble and inspect/clean strainer screen.

Replace if screen is torn or not able to be cleaned.

• Remove and inspect/clean cartridge. Replace if

poppet does not move freely or debris cannot be
removed.

• Remove lower float chamber and inspect internal

parts. Clean out all mud, silt, sediment and debris from
chamber, float mechanism and other waterside
components.

• Inspect equalizing piping. Clean or replace as

required.

• Check all wires for brittle or worn insulation.

• Check for leaks at gasket surfaces and solder joints.

Replace entire unit including equalizing piping every
10 years.

More frequent cleaning or replacement may be
required if used in locations where water treatment is
required or in applications with high make-up water
requirements.

NOTE

Use clean water to rinse components and surfaces. DO

NOT use sharp objects to scrape off any accumulations

of sediment or debris.

Unit is making noise.
a) Cause: Under certain system conditions, there may be

a vibration when the valve mechanism (cartridge poppet)
is slightly open.

Solution: Install a pressure reducing valve, such as the
Bell & Gossett B-38, in the inlet water line before the
feeder valve.

Burner switch not working.

a) Cause: Cam worn or broken.

Solution: Replace cam assembly (CO-106/302900).

b) Cause: Linkages not transferring float movement

to switch.

Solution:

• Linkage pins may be worn or broken which would

require purchasing a new valve assembly
(SA47-101-102/341600).

• Float may be damaged, sediment may have

accumulated in chamber or equalizing piping may be
plugged. Perform testing to determine what the
problem may be and correct.

Water leaking from bellows

a) Cause: Continuous exposure to chemicals or water with

pH higher than 9.0 can cause the solder to deteriorate.

Solution: Remove source of chemicals or consider
replacing control with one that is suitable for the
application.

TROUBLESHOOTING (cont'd)

Advertising