Important – Xylem MM 316E Series 47 and 247 Mechanical Water Feeders User Manual

Page 7

Advertising
background image

STEP 4 - Installing Series 247/247-2 Water Feeder to Boiler

Burner

Boiler

City Water Supply

Return

Header

Series 247
Water
Feeder

Casting
Line

ByPass

Valve

Pipe the Series 247/247-2 water feeder so that
the line on the casting is 3" (76mm) above the
minimum safe operating level as specified by
the boiler manufacturer.

Recommended Piping

STEP 5 - Piping the valve on the Models 47/47-2 and 247/247-2

TO BOILER

By-Pass

Valve

Swing Check

STEP 6 - Electrical Wiring (Only for Series 47-2 & 247-2)

AA

a. Using the flathead screwdriver, loosen the two

(2) screws that secure the switch cover (AA).

Remove cover.

7

!

IMPORTANT

Boiler manufacturer schematics should always be followed. In the event that the boiler manufacturer's schematic
does not exist, or is not available from the boiler manufacturer, refer to the schematics provided in this document.

a. Follow the drawing to the right for piping the valve

to the boiler and city water supply. When piping the
valve, remember to leave room for servicing the
valve.

b. Piping the valve this way will aid in troubleshooting

the valve and piping in the future.