Operation, Electrical ratings – Xylem MM 413F Replacement Head Mechanism With Switch Assembly: 93-HD, 93-M-HD, 93-7B-HD, 93-7B-M-HD, 94-HD 94-M-HD 94-7B-HD 94-7B-M-HD User Manual

Page 2

Advertising
background image

2

Electrical Ratings

Models with 5 or 5-M Switch

Switch Ratings

Burner

Valve

120 VAC

345 VA

0 - 135 ohms @ 24 VAC

240 VAC

Models with 7B or 7B-M Switch

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Pump Off

2

3

/

16

(56)

1

1

/

16

(27)

Pump On

1

1

/

8

(29)

Burner On

1

3

/

8

(35)

1

3

/

8

(35)

Burner Off

0

Switch Settings
Values are ±

1

/

8

" (3mm)

NOTE: Due to the slower operation of some
motorized valves, complete valve opening or
closing may occur at slightly different
levels than indicated above.

Models with 5 or 5-M Switches

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Valve Full

2

3

/

16

(56)

1

1

/

16

(27)

Closed

Valve Full

7

/

8

(22)

Open

Burner On

1

3

/

8

(35)

1

3

/

8

(35)

Burner Off

0

Models with 7B or 7B-M Switches

OPERATION

Maximum Pressure:
Series 93/193:
150 psi (10.5 kg/cm

2

)

Series 94/194: 250 psi (17.6kg/cm

2

)

PUMP

OFF

BURNER

OFF

BURNER

CUT-OFF LEVEL

AT CAST LINE

2

3

/

16

"

(56mm)

PUMP OFF
PUMP ON

(27mm)

1

1

/

16

"

BURNER
“CUT-OFF LEVEL”
AT CAST LINE

BURNER OFF

(35mm)

BURNER ON

1

3

/

8

"

BURNER
“CUT-OFF LEVEL”
AT CAST LINE

BURNER OFF

(35mm)

BURNER ON

1

3

/

8

"

MOTORIZED

VALVE

CLOSED

BURNER

OFF

BURNER

CUT-OFF LEVEL

AT CAST LINE

2

3

/

16

"

(56mm)

MOTORIZED

VALVE

CLOSED

MOTORIZED

VALVE

OPEN

(27mm)

1

1

/

16

"

Pump and Burner Switch Contact Ratings

Voltage

Pilot Duty Only

120 VAC

345 VA

240 VAC

Advertising