d. Based upon the mode of operation (“Flow” or “No-

Flow”) required, complete the appropriate steps to
connect wires to flow switch. Use a Phillip’s head
screwdriver to loosen and tighten switch terminal
screws when attaching wires.

For “Flow” Mode of Operation (Fig. 1)
If the flow switch will be used to actuate a signal,
alarm or other device when

flow occurs, connect

the wire from that device to the “N.O.” contact.
Connect the “Hot” power supply wire to “C” terminal.

For “No Flow” Mode of Operation (Fig. 2)
If the flow switch will be used to actuate a signal,
alarm or other device when

no flow occurs, connect

the wire from that device to the “N.C.” contact.
Connect the “Hot” power supply wire to “C” terminal.

NOTE: Repeat above to connect wires to second
switch on “D” model flow switches.

Flow

Opens

Circuit

Normally

closed

3

Common

1

Flow

Closes

Circuit

2

(

(

Normally

open

(

(

Common

(

(

FS4-3

LINE

LOAD

Fig. 1

HOT

3

1

2

FS4-3

LINE

LOAD

Fig. 2

HOT

3

1

2

c. Determine which switch action is required for the

flow switch.

• “Flow” means that the switch will close circuit

C.-N.O. and open circuit C.-N.C. when flow rate
is increased above setpoint of flow switch.

• “No Flow” means that the switch will open circuit

C.-N.O. and close circuit C.-N.C. when flow rate
is decreased below setpoint of flow switch.