a. Place cover on flow switch and turn on power. Initiate

fluid flow through the system. Observe the device being
activated by the flow switch to determine if device is
operating as required.

b. Turn off fluid flow to determine if device is operating

as required.

c. Repeat initiating and turning off fluid flow several times to

test flow switch and device for proper operation.
- If operating as required, put system into service.
- If not operating as required, flow switch may need

to be adjusted.

OFF

ON

STEP 4 - Testing

STEP 5 - Adjustment

Adjustment is necessary only if required flow/no
flow setpoints are above factory set minimum.

a. Turn off power. Remove electric enclosure

cover.

b. Turn adjusting screw

FRXQWHUclockwise (1/8 turn)

to increase setpoint.

c. Place the cover on the flow switch and turn on

power.

d. Test the operation of the flow switch after

each adjustment.

IMPORTANT: Do not attempt to lower flow switch
setpoint from original factory minimum setting.
Lowering (turning adjusting screw clock

wise)

the setpoint from original factory setting
may cause erratic flow switch operation.