Flow rates, Installation, Step 1 - determine the location of the flow switch – Xylem MM 619F Series FS6 Flow Switch User Manual

Page 3

Advertising
background image

Pipe

Mode of Operation

Size NPT

Flow

No Flow

in. (mm)

Settings

gpm (lpm)

gpm (lpm)

3

4

(20)

Factory or

or

Minimum

.12

(.45)

.06

(.23)

1

(25)

Maximum

2.5

(9.46)

1.5 (5.68)

FLOW RATES

Settings will vary when used to sense flow of other
fluids.

3

NOTE: DO NOT USE LIQUID FLOW

SWITCHES ON SYSTEMS WITH
FLOW VELOCITY GREATER THAN
10 FEET (3M) PER SECOND.

Flow Rates

Values are ± 10%

Max. Flow

Rate gpm (lpm)

w/o Paddle

Damage

INSTALLATION –

STEP 1 - Determine the Location of the Flow Switch

5 x D

MINIMUM

5 x D

MINIMUM

D= PIPE DIAMETER

3/4

" or 1" PIPE

D

• The flow switch should be located in a horizontal

section of pipe where there is a straight horizontal
run of at least 5 pipe diameters on each side of the
flow switch.

• The flow switch must be installed in the upright

position as shown with arrow mark on side of casting
in the same direction as fluid will flow.

• Some system conditions that require more than 5

pipe diameters are high viscosity fluid and high fluid
velocity.

70 (265)

GPM CAPACITY

FS6 SERIES PRESSURE DROP

90

80

70

60

50

40

30

20

10

D

IF

F

E

R

E

N

T

IA

L

P

R

E

S

S

U

R

E

10

20

30

40

50

60

70

FS6 VELOCITIES IN FPS

40

30

20

10

VELOCITY IN FEET PER SECOND

GPM CAPACITY

10

20

30

40

50

60

70

FS

6-

3

/

4

"

PIPE

FS6

-1"

PIPE

NOTE: THIS PRODUCT IS NOT INTENDED

FOR USE IN POTABLE WATER

APPLICATIONS.

calculated using clean water in a horizontal pipe.

Flow rates required to activate the flow switch

are shown in chart below.These values were