STEP 1 - Removal and Replacement of Contacts and Terminal Panels

a. Turn power off to boiler and all controls.

Allow boiler to cool to 80˚F (27˚C) and
reduce the pressure to 0 psi (0 bar).

BURNER

SWITCH

LEVER

STOPS

A

C

E

TOWER TUBE

FITTING HUB

SWITCH
HOUSING

TERMINAL
CONNECTIONS

SWITCH
COVER

PUMP

TERMINAL

PANEL

BURNER

TERMINAL

PANEL

CONDUIT
CONNECTOR

NAMEPLATE

NAME PLATE

BASE
PLATE

B

D

b. Remove Switch Assembly, Terminal

Panels and Switch Housing

• Remove two screws (A) and lift off switch

cover.

• Identify terminal connections for rewiring

and then disconnect all wires from terminal
panels.

• Remove conduit connector and wire from

integral fitting hub.

• Remove four hex nuts (B) and carefully lift

switch assembly up and off tower tube.

• Remove two screws (C) and remove

nameplate.

• Loosen and remove four screws (E) that

hold pump and burner terminal panels in
place. Do not remove terminal panels at
this time.

• Reach through nameplate opening and hold

burner switch lever about midway
between upper and lower stops to move
contact arms into correct (upright) position.
With contact arms in upright position, carefully
remove burner terminal panel.

• Reach through nameplate opening and hold

pump switch lever about midway
between upper and lower stops to move
contact arms into correct (upright) position.
With contact arms in upright position, carefully
remove pump terminal panel.

• Loosen four screws (E) and carefully lift

switch housing up off base plate.

There may be more than one source of power to
the boiler.

!

CAUTION